Critical Power

Safety Statements

Do not install this equipment over combustible surfaces.
Rules and Regulations - Follow all national and local rules and regulations when making field connections.
Compression Connectors
U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified
field-wire conductors.
All installations - apply the appropriate connector to the correct size conductor as specified by the
connector manufacturer, using only the connector manufacturer's recommended or approved tooling for
that connector.
Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.
Circuit Breakers and Fuses
Use only those specified in the equipment ordering guide.
Size as required by the National Electric Code (NEC) and/or local codes.
Safety Tested Limits – Refer to the equipment ratings to assure current does not exceed:
Continuous Load (List 1) - 60% of protector rating.
o
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
o
GMT Style Fuses - Use only fuses provided with safety caps.
Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.
Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit
breaker rating.
AC and DC input disconnect/protection - Provide accessible devices to remove input power in an
emergency.
Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.
· Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect
to the cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding
network.
Déclarations de sécurité
N'installez pas cet équipement sur des surfaces combustibles.
Règles et règlements-respectez toutes les règles et réglementations nationales et locales lors de la
réalisation de connexions sur le terrain.
Connecteurs de compression
Installations des États-Unis ou du Canada-utiliser des connecteurs de compression répertoriés/certifiés
pour mettre fin aux conducteurs de fil de champ répertoriés/certifiés.
Toutes les installations-appliquer le connecteur approprié au conducteur de taille correct tel que spécifié
par le fabricant du connecteur, en utilisant uniquement l'outillage recommandé ou approuvé par le
fabricant du connecteur pour ce connecteur.
Fixation de la connexion électrique: Serrez les valeurs spécifiées sur les étiquettes ou dans la
documentation du produit.
Robe de câble-robe pour éviter d'endommager les conducteurs et une contrainte excessive sur les
connecteurs.
Disjoncteurs et fusibles
Utilisez uniquement ceux spécifiés dans le Guide de commande de l'équipement.
SPS –48V Slimline Power Shelf
Quick Start Guide
SPS J200703 L005 – Quick Start Guide