9.4

Special Internal Outputs in the CPU module

The status information on an EH-ETH module is stored in the special internal outputs area of CPU module
shown in Table 9.4.1.
[ [ [ [ WRF020, WRF022, WRF024] ] ] ]
Bit
0
ASR1 connection status bit
1
ASR2 connection status bit
2
ASR3 connection status bit
3
ASR4 connection status bit
4
ASR5 connection status bit
5
ASR6 connection status bit
6
ASR1 close request bit
7
ASR2 close request bit
8
ASR3 close request bit
9
ASR4 close request bit
10
ASR5 close request bit
11
ASR6 close request bit
12
Task code port1 status bit
13
Task code port2 status bit
14
Task code port3 status bit
15
Task code port4 status bit
[ [ [ [ WRF021, WRF023, WRF025] ] ] ]
Bit
0
ASR1 open error status bit
1
ASR2 open error status bit
2
ASR3 open error status bit
3
ASR4 open error status bit
4
ASR5 open error status bit
5
ASR6 open error status bit
6, 7
Reserved
8
ERR LED status bit
9
I.ERR LED status bit
10
ASR enable status bit
11
AVR flag display bit
12
Ethernet information error bit
13
Sum error bit
14
Operation mode bit
15
Fatal error bit
Table9.4.1 Status information on an EH-ETH module
I/O No.
Target slots No.
WRF020
Slot 0
WRF021
WRF022
Slot 1
WRF023
WRF024
Slot 2
WRF025
Explanation
0: Closed,
0: No request,
0: Closed,
Explanation
0: Without error,
0: Turn off
0: Disable
The AVR flag of MDSR is displayed.
0: Without error
0: Normal
0: Without error
9-6
Chapter 9 Maintenance, check, error
1: Open
1: Request
1: Open
1: Error
Always "0"
1: Turn on
1: Enable
1: Error
1: IP address setting mode
1: Error

Advertisement