Download Print this page

Honeywell C7046C Product Data page 4

Solid state economizer system, consisting of discharge air sensor or mixed air sensor, solid state enthalpy sensor, solid state temperature sensor, damper actuators, thermostat and solid state economizer logic module
Hide thumbs Also See for C7046C:

Advertisement

SOLID STATE ECONOMIZER SYSTEM
Approval:
Underwriters Laboratories Inc. Flammability Rating:
UL94-5V.
Dimensions:
See Fig. 3.
5/16 (8)
3-5/32
(80)
2-3/4
(70)
9/16
7/32
(14)
(6)
1 (25)
Fig. 3. Approximate dimensions of C7400A Solid State
Enthalpy Sensor/C7650A Solid State
Temperature Sensor in in. (mm).
M7415A, M8405A Damper Actuators
Provides control of economizer systems, ventilation dampers
and combustion air dampers used in residential or
commercial HVAC equipment.
Model
Voltage (Vac)
Number
50/60 Hz
b,c
M7415A
24
b,d
M8405A
24
a
Timing with 60 Hz power.
b
Spring return.
c
Modulating.
d
Three-position with field adjustable minimum position control.
7/16
3-1/2 (89)
(11)
TOP VIEW
Fig. 4. Approximate dimensions of M7415A and M8405A in in. (mm).
63-2484—1
+
S
3-7/8 (96)
M9096
Table 1. M7415A/M7405A Actuator Specifications.
Power (Vac)
Timing
(Drive)
(Hold)
(sec)
8
5
90
7
3
90
4-1/2 (114)
4-1/32
4-1/2
(102)
(114)
4-1/2
(114)
5
(127)
2-1/4 (57)
1-1/4
(32)
5-3/16 (132)
Actuator Rotation:
Closed position is the limit of clockwise rotation; open position
is the limit of counterclockwise rotation as viewed from the
shaft end of the motor. These motors are shipped with the
shaft in the closed position.
Auxiliary Switch Rating (M8405A only):
24 Vac, 20 VA inrush, 20 VA run (R8222 or equivalent load).
Terminal Connections:
1/4 in. (6 mm) male quick connect terminals mounted on
actuator. Terminal arrangement is dependent on actuator
model.
Ambient Operating Temperature Range:
-40°F to +125°F (-40°C to +52°C).
Voltage and Timing:
See Table 1.
Dimensions:
See Fig. 4.
Shaft:
Single-ended drive shaft with crank arm supplied.
Flammability Rating:
Underwriters Laboratories Inc. UL94-5V.
Approval:
Underwriters Laboratories Inc.
Component Recognized: File No. E4436, Guide No. XAPX2,
Vol. 9, Section 1, 7-25-83.
Torque
Stroke
a
(°)
(lb-in.) (N•m)
90
25
2.8
90
25
2.8
SIDE VIEW
4
Open Rotation
Spring Return
(Shaft End View)
(Shaft End View)
ccw
cw
ccw
cw
1/4 (6)
1-3/8 (35)
3-1/8 (79)
POWER END VIEW
M3851

Hide quick links:

Advertisement

loading