Honeywell AQS51-KAM Product Data page 3

Combined co2-/temperature duct sensor/controller
Table of Contents

Advertisement

Analog outputs
Digital relay output
Dimensions
Zigzag traces
(accessible after
removing the cover)
Shortage with a
screwdriver simulates
pushing of push button
DIMENSIONS
84
25
5
55
AQS51/61-KAM COMBINED CO
Output signal
Resolution
D/A conversion accuracy
Protection
Customization of P+I controller
Single pole, double throw
(SPDT) switching, potential free
contact.
Factory adjusted switching
setpoint and differential
Sensor housing
Sampling probe
MENU Zigzag traces
Fig. 1 Dimensions in mm
-/TEMPERATURE DUCT SENSOR/CONTROLLER
2
0...10 Vdc / 2...10 Vdc, impedance 100 Ω
or 0...20 mA / 4...20 mA, load ≤500 Ω
10mV (10Bits)
±2% of output voltage, +0.1 V
±2% of output current, ±0.3 mA
PTC fuse (auto reset), short-circuit proof
Both outputs can be configured to any sensor mix (CO
temperature + digital input of 5 proportional ranges with
priorities and offsets, using the PC software STRATEGY,
Version 3)
1A/50 Vac (50VA) or 1 A / 24 Vdc (30 W)
Relay activated: ≥1000 ppm
Relay deactivated: ≤900 ppm
(84 x 142 x 46) mm
203 mm
Toggles between the following 6 display modes on
the 4-digit display:
- CO
and temperature alternating
2
- Error code
- CO
in ppm
2
- Temperature in °C
- Analog output 1
- Analog output 2
203
+
2
46
42
EN0B-1023 GE02R0700