Toshiba MMD- AP0091BH Installation Manual page 19

Super modular multi system air conditioner
Table of Contents

Advertisement

Change of lighting term of filter sign
According to the installation condition, the lighting term
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
1
2
3
4
5
(
• For the item code in Procedure
• For the [Set data] in Procedure
of filter sign lighting terme from the following table.
Setup data
0000
0001
0002
2500H (At shipment from factory)
0003
5000H
0004
10000H
To secure better effect of heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the room,
the detection temperature of heating can be raised.
Also use a circulator, etc. to circulate heat air near the
ceiling.
Follow to the basic operation procedure
1
2
3
4
5
(
• For the item code in Procedure
• For the set data in Procedure
of shift value of detection temperature to be set up
from the table below.
Setup data
0000
0001
0002
0003
0004
0005
0006
6
).
3
, specify [01].
4
, select the setup data
Filter sign lighting term
None
150H
6
).
3
, specify [06].
4
, select the setup data
Detection temp shift value
No shift
+1°C
+2°C (At shipment from factory)
+3°C
+4°C
+5°C
+6°C
Group control
In a group control, a remote controller can control
up to maximum 8 units.
• For cabling procedure and cables of the individual
line (Identical refrigerant line) system, refer to
"Electric work" in this Manual.
• Cabling between indoor units in a group is
performed in the following procedure.
Connect the indoor units by connecting the
remote controller inter-unit cables from the
remote controller terminal blocks (A, B) of the
indoor unit connected with a remote controller to
the remote controller terminal blocks (A, B) of the
other indoor unit. (No polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
19

Advertisement

Table of Contents
loading

Table of Contents