Toshiba MMD- AP0091BH Installation Manual page 18

Super modular multi system air conditioner
Table of Contents

Advertisement

7
APPLICABLE CONTROLS
Setup of outside static pressure
Be sure to set up a tap change based upon the
resistance (outside static pressure) of the duct to be
connected.
To set up a tap change, follow to the basic operation
1
2
3
procedure (
• Specify [5d] to the item code in procedure
• For the setup data of procedure
data of the outside static pressure to be set up from
the following table.
In case of remote controller-less (Group control)
For setup to the high ceiling, there is selecting method by exchanging the short plugs on the indoor
microcomputer P.C. board as shown in the following table other than selecting method by standard wired remote
controller
(sold separately). Utilize this method for remote controller-less (Group control) case.
∗ However, when the setup to high ceiling has been once exchanged, it is required for returning it to 0000 to
change the short plug to the standard (at shipment) position and rewrite data to the setup data 0000 from the
wired remote controller sold separately though setup to 0001 or 0003 are freely available.
To incorporate a filter sold separately for reference
• Select by exchange of short plugs on the indoor
microcomputer P.C. board.
Short plug position
Set data
Short
Open
CN112 CN111 CN110
0000
CN112 CN111 CN110
0001
CN112 CN111 CN110
0003
4
5
6
).
3
.
4
, select a setup
Filter sold separately
Standard filter
(At shipment)
Super long life filter
High-efficiency filter (65%)
High-efficiency filter (90%)
<Change on wired remote controller>
Setup data
0000
40Pa
0001
70Pa *1
0003
100Pa *2
0006
20Pa
*1: 65Pa for Model AP0481BH, AP0561BH
*2: 90Pa for Model AP0481BH, AP0561BH
• Short plug position
(CN112, CN111, CN110 from the left)
18
Outside static pressure
Standard (At shipment)
High static pressure 1
High static pressure 2
High static pressure