(10) Checks Prior to Automatic Addressing

* When an outdoor unit alarm is displayed, perform the following checks after troubleshooting.
1
Indoor/outdoor power
source
2
Indoor/outdoor control
wires
3
Outdoor settings
*1: Terminal resistor is basically "ON(SHORT)" for one unit only, but depending on the installation status can be
set to "ON(SHORT)" for up to 3 units.
•2-3
Backup connectors and terminals for indoor/outdoor control wires (for communication)
Equipment
Outdoor Unit
Indoor unit
System controller
Multi-controller
Intelligent controller
AMY adapter
* For a system linking wiring systems, if the systems are connected to water heat exchange unit, depending on
the state of the hot / cold water, automatic address alarm may occur.
If this happens, remove the link wiring and set address individually.
1-1
Indoor and outdoor units turned on?
Have the inside/outside control wires been laid? Is there a
2-1
break or disconnection of wires?
Was a high voltage (200 V AC), etc. applied to the control
wire circuit?
2-2
Has a fuse on the control board blown?
[Confi rmation of each outdoor and indoor unit]
There is a problem with the wiring of the power cable and indoor/outdoor control wires.
2-3
Turn off the power, check and repair faulty wiring, and then connect all indoor/outdoor
control wires to the backup control board and controller.
Does the setting of connected indoor unit count (No. 10)
3-1
on the outdoor control board match the actual count of
connected indoor units?
Are the indoor/outdoor control wires connected to multiple
3-2
outdoor units?
(Wire-linked?)
Is S010 (terminal resistor ON/OFF switch) on the outdoor
3-3
main board set to ON for only one outdoor unit and set to OFF
for all other outdoor units *1?
3-4
Are there any duplicate settings for outdoor units?
For link wiring, set a system address for each outdoor unit in the order of 1, 2, 3, and then
3-5
perform automatic addressing.
3-6
Perform automatic addressing.
Primary
CN045 (for communication)
CN040(0C)
Terminal block No. A7 and B7
Terminal plate No. 2 (U2)
Terminal block No. 2
JP3-A side
Backup
CN046 (EMG)
CN044(EMG)
Terminal plate No. 3 (Indoor/outdoor backup control wire)
Terminal block No. 3
Terminal block No. A6 and B6
JP3-B side
V–53
Yes 2-1
No
Turn on the power
Yes 2-2
Wiring and
No
connection
Yes 2-3
No
3-1
Yes 3-2
No
Correct the setting
Yes 3-3
No
3-6
Yes 3-4
No
Correct the setting
Yes 3-5
No
3-6