Panasonic 2WAY Multi Technical & Service Manual page 139

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

6) Error log clear
Clears all of the error log and temporary stop causes for this outdoor unit.
Operation method: Press the SET (S007) key for one second.
 →  → 
(clearing)
7) Error (alarm) code list
Error
Error (Alarm) Contents
Code
A00
No error occurred
(System A: Engine system protective device
operation)
A01
Engine oil pressure error
A02
Engine oil error
A03
Engine high-revolution error
A04
Engine low-revolution error
A05
Ignition power supply error
A06
Engine start failure
A07
Fuel gas valve error
A08
Engine stall
A10
High exhaust gas temperature
A11
Engine oil level error
A14
Engine oil pressure switch error
A15
Starter power supply output short circuit
A16
Starter lock
A17
CT error (starter current detection failure)
A19
Low coolant temperature
A20
High coolant temperature
A21
Coolant level error
A22
Coolant pump error
A23
Crankshaft angle sensor error
A24
Camshaft angle sensor error
A25
Clutch error
A26
Flameout error
A27
Catalyst temperature error (for only models fi tted
with a catalyst)
A28
Generator error (detected only with HP)
A29
Converter error (detected only with HP)
(System E: Communication system errors)
E01
Remote controller receive failure
E02
Remote controller transmission failure
E03
Indoor unit receive failure from the remote
controller (central)
E04
Indoor unit receive failure from the outdoor unit
E05
Indoor unit transmission failure to outdoor unit
E06
Outdoor unit receive failure from the indoor unit
E07
Outdoor unit transmission failure to the indoor
unit
E08
Duplicate indoor unit address setting
E09
Multiple main remote controller units set
E10
DC fan driver communication error
E11
Indoor unit receive failure from the signal output
board
E12
Auto-address start forbidden due to auto-
address in progress
E13
Indoor unit transmission failure to the remote
controller
E15
Automatic address alarm (too few units)
E16
Automatic address alarm (too many units)
E18
Group control wiring communication failure
E20
No indoor unit
E24
Communication failure between outdoor units
(only detected with W-Multi)
E26
Inconsistency in number of outdoor units (only
detected with W-Multi)
E31
Communication failure between units
(complete)
Error
Code
(System F: Defective sensors, memories and
other parts)
F01
Indoor unit heat exchanger inlet temperature
sensor error
E1 sensor error (when the water heat exchanger
unit is connected)
F02
Anti-icing sensor error (when the water heat
exchanger unit is connected)
F03
Indoor unit heat exchanger outlet temperature
sensor error
E3 sensor error (when the water heat exchanger
unit is connected)
F04
Compressor outlet temperature sensor error
F06
Outdoor unit heat exchanger inlet temperature
sensor error
Outdoor unit heat exchanger 2 inlet temperature
sensor error (3WAY only)
F08
Outside air temperature sensor error
Fl0
Indoor unit intake temperature sensor error
Water intake temperature sensor error (when the
water heat exchanger unit is connected)
F11
Indoor unit discharge temperature sensor error
Water discharge temperature sensor error (when
the water heat exchanger unit is connected)
F12
Compressor inlet temperature sensor error
F13
Coolant temperature sensor error
F16
Compressor inlet/outlet pressure sensor error
F18
Exhaust gas temperature sensor error
F20
Clutch coil temperature sensor error
F21
Clutch 2 coil temperature sensor error
F29
Indoor unit non-volatile memory (EEPROM) error
F30
Real time clock (RTC) function error
F31
Outdoor unit non-volatile memory (EEPROM)
error
(System L: Duplicate address and other setting
defects)
L02
Inconsistencies in indoor/outdoor units (non-GHP
equipment connected)
L03
Multiple main units set for group control
L04
Duplicate system (outdoor unit) address setting
L05
Duplicate indoor unit priority setting (priority
indoor unit)
L06
Duplicate indoor unit priority setting (excluding
priority indoor units)
L07
Group control wiring exists for individual-control
indoor unit
L08
Indoor unit address not set
L09
Indoor unit capacity not set
L10
Outdoor unit capacity not set
L13
Indoor unit model setting defect
L15
Indoor unit pairing defect
L16
Water heat exchanger unit setting defect (when
the water heat exchanger unit is connected)
L19
Duplicated water heat exchanger unit parallel
address (when the water heat exchanger unit is
connected)
L21
Gas type setting failure
V–20
Error (Alarm) Contents