9.1.3 Output signals on voltage-free contacts

The interface board provides 6 voltage free relay contacts giving some UPS critical alarms and
operation mode.
These signals are available either on connector J2- (sub D, female 25 pin) or terminal blocks X1.
The meaning of the alarms on the free contacts in standard configuration (default) is the following:
X1 / 1, 2, 3
or
X1 / 4, 5, 6
or
X1 / 7, 8, 9
or
X1 / 12, 13, 14
or
X1 / 15, 16, 17
or
X1 / 18, 19, 20
or
In case different alarms or operating status are required, they can be configured on the same terminals
via software from the control panel.
The configuration can be changed in parameters mode by a trained operator using the appropriate
password.
NOTE !
The programmable signals on X1 and J2 will be disabled with Q1 open, with the
exception of the signals for "16 - Manual Bypass Q2 ON" and "26 - EPO".

9.1.4 Programmable input free contacts

Some programmable UPS functions (indicated in Section 9.1), can be activated by closing an external
contact, if connected, on:
X1 / 10, 21
or
X1 / 11, 22
or
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
J2 / 1, 2, 3
(NO, C, NC)
J2 / 4, 5, 6
(NO, C, NC)
J2 / 7, 8, 9
(NO, C, NC)
J2 / 14, 15, 16
(NO, C, NC)
J2 / 17, 18, 19
(NO, C, NC)
J2 / 20, 21, 22
(NO, C, NC)
J2 / 10, 23
J2 / 11, 24
Mains Failure
Load on Inverter
Stop Operations
Load on Mains
General Alarm
Acoustic Alarm
User Input 1 (default = Not used)
User Input 2 (default = Emergency GEN ON)
Operating Manual SitePro 10-15-20-30-40 kVA / S8
(def. Parameter RL=1)
(def. Parameter RL=3)
(def. Parameter RL=5)
(def. Parameter RL=2)
(def. Parameter RL=4)
(def. Parameter RL=6)
Page 87/99