Serial Port J3; Output Free Potential Contacts - GE SG300 Installation Manual

Hide thumbs Also See for SG300:
Table of Contents

Advertisement

4.1.1 Serial Port J3

1
2
3
4
Fig. 4.1.1-1 Serial port J3
The serial port J3 - RS232 is enabled
on all the units of the parallel system.

4.1.2 Output free potential contacts

The interface board provides 6 voltage free relay contacts giving some UPS critical alarms and
operation mode.
These signals are available either on connector J2- (sub D, female 25 pin) or terminal blocks X1.
The meaning of the alarms on the free contacts in standard configuration (default) is the following:
X1 / 1, 2, 3
X1 / 4, 5, 6
X1 / 7, 8, 9
X1 / 12, 13, 14
X1 / 15, 16, 17
X1 / 18, 19, 20
In case different alarms or operating status are required, they can be configured on the same terminals
via software from the control panel.
The configuration can be changed in parameters mode by a trained operator using the appropriate
password.
NOTE !
The programmable signals on X1 and J2 will be disabled with Q1 open, with the
exception of the signals for "16 - Manual Bypass ON" and "26 - EPO".
Modifications reserved
OPM_SGS_ISG_M22_M30_2US_V010.doc
1
2
3
J3
4
or
J2 / 1, 2, 3
or
J2 / 4, 5, 6
J2 / 7, 8, 9
or
or
J2 / 14, 15, 16
J2 / 17, 18, 19
or
or
J2 / 20, 21, 22
Serial port J3 - RS-232 (sub D, female 9 pin) that
allows:
Total remote management of the system using
software GE Power Diagnostics, GE Data Protection or
GE Service Software for system protection and
management of the UPS systems.
Fig. 4.1.1-2 Serial port J3 connection to PC with RS232 1:1 cable DB9m – DB9f
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
Utility Failure
Load on Inverter
Stop Operations
Load on Utility
General Alarm
Acoustic Alarm
Page 37/40
Installation Guide SG Series 225 & 300 UL S2