Wireless Alarm Bar Installation Guide
3.2. Wireless Alarm Bar Wiring
The Wireless Alarm Bar already has most wiring done at the factory. It is only necessary to connect
the power supply wires and grounding (according to local requirements). Power and internal
grounding wires must be fed through a connector at the bottom of the unit.
IMPORTANT!
Prior to factory shipment, the RAEPoint is tested. However, the instrument should be tested after
installation.
3.2.1. Complete Wireless Alarm Bar Wiring Diagram
The schematic diagram below shows internal wiring of the Wireless Alarm Bar. Refer to the
diagram on page 13 for power connections.
Note: Thermistors are pre-installed in the Junction Box to protect the relays.
Wires must be fed in
through a 1/2" NPT insert
(UL-certified). Conduit
seals are required within
18" (45 cm) of conduit
entrances for Group C
hazardous locations.
10