28.12

Remote Operation

In a redundant system, the operation target of remote operations (with the engineering tool) depends on the operation mode
and method.
Operation mode
Remote operation

Remote RUN, remote STOP, remote PAUSE

Backup mode
The CPU module operating status of a system specified in the
transfer setup of the engineering tool or both systems can be
changed.
Separate mode
The CPU module operating status of a system specified in the transfer setup of the engineering tool can be changed.
Remote RUN, remote STOP, remote PAUSE
The following describes the remote RUN, remote STOP, and remote PAUSE operations in a redundant system.
In backup mode
The CPU module operating status of a system specified in the transfer setup of the engineering tool or both systems can be
changed.
■Remote operation performed on the CPU module of a system specified in the transfer setup of
the engineering tool
When any of the following items is selected in "Execution Target", the remote operation is performed only on the CPU module
of a system specified in the transfer setup of the engineering tool.
• Currently Specified Station
• All Stations Specified
• Specify Group No.
[Online]  [Remote Operation]
■Remote operation performed on both systems
When the following item is selected in "Specify Execution Target", the remote operation is performed on the CPU modules of
both systems.
• Specify Both Systems
[Online]  [Remote Operation]
When "Specify Redundant CPU" is set to "Not Specified" in the transfer setup, select "All Stations Specified" or
"Specified Group" to perform a remote operation on the CPU modules of both systems.
In separate mode
The CPU module operating status of a system specified in the transfer setup of the engineering tool can be changed. (
Page 491 Remote operation performed on the CPU module of a system specified in the transfer setup of the engineering tool)
Remote RESET
The CPU modules of both systems can be reset by performing
the remote RESET operation on the control system CPU
module. Only the standby system CPU module can be reset by
performing the remote RESET operation on the standby system
CPU module.
28.12 Remote Operation
28
28 FUNCTIONS
491