Download Print this page

Honeywell SPM Flex Quick Start Manual page 2

Single point monitor gas detector
Hide thumbs Also See for SPM Flex:

Advertisement

Opening the Chemcassette
cartridge door
®
Figure 8: Opening the Chemcassette cartridge door
Menu Map
Main Menu
Login/Logout
Reset Alarms & Faults
Reset all
Monitor Mode
monitor mode
Change Chemcassette
Review Mode
Event
History
Maintenance
Summary
Setup
General
Test
Optics
Verification
Power Off
Figure 10. SPM Flex menu map
Loading a Chemcassette
Figure 9: Loading a Chemcassette cartridge
Silence
audio alarm
Enter
Out of
monitor mode
Chem-
Gas
Additional
Output
Network
cassette
Settings
Status
State
Inhibit
4-20 mA
Flow Char-
Open/Close
Update
Program
Current Loop
acterization
Gate
Monitoring
Latching
Outputs
Network
Security
Force
Force
Simulate
Relay
4-20 mA
1.
Navigate to the "Change Chemcassette" menu option.
cartridge
®
2.
Follow the on-screen instructions to install or change the cartridge.
3.
Remove the paper optics card from the gate.
4.
Insert the Chemcassette cartridge in the detector (it will fit in only one
orientation). The take-up spindle rotates slightly to allow the cartridge
to snap into place easily.
5.
Close the cover.
6.
A summary of the current configuration will be displayed. Select
either to enter monitor mode or to remain out of monitor mode (i.e.,
idle).
Removing a Chemcassette
1.
Navigate to Maintenance > Open/Close gate.
2.
Select "Open Gate."
3.
Remove the cartridge.
4.
Select "Close Gate."
5.
Inert the optics card in the gate if the detector will be stored or
transported.
Changing the selected gas
1.
While out of monitor mode, navigate to Set-up > Monitoring > Gas.
2.
Select "Current gas" and pick the desired gas from the selection box
3.
Select "Save."
Entering monitor mode
From the main menu, navigate to the "Monitor Mode" option and select
"Enter monitor mode."
1.
If a Chemcassette cartridge has been installed, the detector will enter
Monitor Mode.
2.
If a Chemcassette cartridge has not been installed, a user with
the necessary passcode can inititate the Chemcassette wizard.
Otherwise, the detector will not enter monitor mode.
Wiring and tubing
The SPM Flex detector has flexible installation options to allow the user to
select the one most suitable for a specific application. The 4-20 mA output
is a three-wire connection that is configurable as sink, source, or isolated.
The detector is equipped with three relays.
Trend/Plot
Software
Description
Tubing length, ft. (m)
Transport time (sec)
Inlet
Flow rate (cc/min.)
Configuration
Manager
Tubing OD, in. (mm)
Tubing ID, in. (mm)
Tubing length, ft. (m)
Outlet
Tubing OD, in. (mm)
Tubing ID, in. (mm)
The overall maximum load on the pump between the inlet and the exhaust should not exceed 10 inches H 2 O.
Use Teflon Fluorinated Ethylene Polymer (FEP) tubing to ensure proper
sample transport.
The SPM Flex detector is supplied with the standard Ethernet, power,
and communications connectors installed. The Ethernet connector can
be removed and provides a 1-inch conduit port which allows a direct
connection to the PCB communication terminals. Refer to the Wiring and
tubing section of the user manual for more information.
Attaching the shoulder strap
cartridge
®
If the shoulder strap is to be used with a portable detector, attach its
spring clips to each of the rings on the detector's handle.
Product label
Figure 11. SPM Flex label
Have questions?
Honeywell Analytics
Sample Tubing Specifications
405 Barclay Boulevard
Maximum
Lincolnshire, Ilinois 60069
Tel: +1 847 955 8200
100 (30)
66 (20)
33 (10)
0
Toll free: +1 800 538 0363
19
13
7
1
Fax: +1 847 955 8208
700-1200 (flow is set and controlled per calibration)
detectgas@honeywell.com
0.25 (6.35)
0.125 (3.18)
100 (30)
0.25 (6.35)
0.188 (4.76)
NOTE
!