GSMX4G / GSMXCN4G Installation and Setup Guide
Modes of Operation
The GSMX4G is for control panels that support ECP communication.
•
The control panel treats the communicator as an ECP device, so
•
ensure to program the control panel with the communicator's device
address.
4204 Mode, and two 4204 Mode operation.
•
Supervision and Fault Detection
Network communication failure – In the event the AlarmNet
•
network does not hear a supervisory message from the communica-
tor within a specified time ("Supervision" option, 24 hours, 30 days,
or none), AlarmNet notifies the central station of a communication
failure.
Communication path failure – In the event the communicator
•
detects a communication path failure, the control panel can be
notified of a trouble condition with the communicator after a
specified time has elapsed.
Specifications
Dimensions:
4 x 7 x 1.75 inches
Input Voltage:
12VDC (powered via the ECP bus.)
Standby Current:
65mA
Active Current:
380mA
Operating temperature:
–20º to +55ºC, for UL/ULC installations 0ºC to +49ºC
Storage temperature:
–40º to +70ºC
Humidity:
0 to 95% relative humidity, non-condensing
(UL installations 0% to 85%; for ULC installations 0% to 93%)
Altitude:
to 10,000 ft. operating, to 40,000 ft. storage
Frequency Bands
2G
GMS/GPRS/EDGE
3G/4G
UMTS/HSPA+
Output Power
2G
GPRS
+33dBm, GMSK modulation
EDGE
+27dBm, 8-PSK modulation
3G
UMTS
+24dBm, QPSK modulation
WCDMA
+24dBm, QPSK modulation
4G
HSPA+
+24dBm, 64 QAM modulation
WCDMA
+24dBm, 64 QAM modulation
Quad Band, 850/900/1800/1900 MHz
Band V, Band II
– 2 –