Settings Files Converting A Saved Mif Ii Or Miv Ii Setpoint File - GE Multilin 3 Series Manual

Retrofits from m & mii family, 239, 735/737, mlj, & tov relays
Table of Contents

Advertisement

CHAPTER 2: CONVERTING SETTINGS FILES
Note
3 SERIES RETROFIT – INSTRUCTION MANUAL
2.2
Converting a saved MIF II or MIV II setpoint file
The Enervista 3 Series Setup software allows the user to create new setpoint files based on
existing MII setpoint files. These can be uploaded to a relay at a later date. The following
procedure illustrates how to convert existing MII setpoint files.
Only MIF II and MIV II setpoint files from EnerVista MII Setup version 2.70 and firmware
versions listed at the beginning of this chapter are supported for conversion.
1.
Install and start the latest version of the EnerVista 3 SeriesSetup software (available
from the GE EnerVista CD or Website). (See the 350 Feeder Protection Instruction
Manual for more information.)
2.
Select Offline > New Settings File from the top menu bar. The following box appears,
allowing for the configuration of the setpoint file for the correct firmware version and
relay order code.
It is important to define the correct firmware version and order code to ensure that
only available setpoints are downloaded into the relay.
CONVERTING A SAVED MIF II OR MIV II SETPOINT FILE
25