Honeywell C7089 Installation Instructions page 3

Outdoor sensor (use with th8000 and th7000 thermostats)
Hide thumbs Also See for C7089:

Advertisement

OPERATION
Once installed and the Thermostat installer Setup
Number 8346 is set to 1 or 2, the outside temperature
can be displayed on the thermostat. See Fig. 3.
7
TUE
iC
Heat On
Foltowing
Schedule
HE_
Outside
-t.I I_- _,,
t-- t--I
rT-S
t----!----I
M19971
Fig.
3. Outside
temperature
reading
on
TH8000
Series
Thermostat.
C7089
OUTDOOR
SENSOR
The C7089 Outdoor Sensor converts outdoor ambient
temperature
to a resistance that the thermostat can
interpret.
The C7089
has a negative
temperarule
coefficient
(TC), which
llleans
that lesistance
decreases
as
tile rempelature
incleases.
See Table
1
CHECKOUT
Allow C7089B Outdoor Sensor to absorb outdoor air for a
minimum of twenty minutes before taking a reading.
With an accurate thermometer (:t:l°F [O.5°C]) measure
the temperature
at the sensor location, allowing time for
the thermometer
to stabilize before reading.
To verify sensor resistance, remove one wire from one of
the C7089 60-in. leadwires. Use an ohmmeter to
measure the resistance across the sensor. Then verify
the sensor accuracy with the temperature/resistance
in
Table 1.
CALIBRATION
The
C7089
Ourdool
Seilsor
is caliblared
at tile fucroly
and
can-
nor be recalibrated in tile field
-2O
-18
-16
-14
-12
-10
-8
-6
-4
-2
O
2
4
6
8
Table
1. Sensor
Resistance
at Outdoor
Temperature.
Outdoor
Temperature
°F
°C
-28.9
-27.8
-26.7
-25.6
-24.4
-23.3
-22.2
-21.1
-20.0
-18.9
-17.8
-16.7
-15.6
-14.4
-13.3
Ohms
of
Resistance
106926
100923
95310
90058
85124
80485
76137
72060
68237
64631
61246
58066
55077
53358
49598
3