"A" Group: Standard Functions

The inverter provides flexibility in how you control Run/Stop operation and set the
output frequency (motor speed). It has other control sources that can override the A001
/ A002 settings. Parameter A001 sets the source selection for the inverter's output
frequency. Parameter A002 selects the Run command source (for FW or RV Run
commands). The default settings use the input terminals for –FE (European) models,
and the keypad for –FU (USA) models.
Func.
Code
A001
A201
A002
A202
Frequency Source Setting – For parameter A001, the following table provides a further
description of each option, and a reference to other page(s) for more information.
More user manuals on
"A" Function
Name /
SRW Display
Frequency source setting
F-COM
VR
Frequency source setting,
2nd motor
2F-COM
VR
Run command source setting
OPE-Mode
REM
Run command source setting,
2nd motor
OPE-Mode
REM
Code
00
Keypad potentiometer – The range of rotation of the knob
matches the range defined by B082 (Start frequency
adjustment) to A004 (Maximum frequency setting)
01
Control terminal – The active analog input signal on analog
terminals [O] or [OI] sets the output frequency
02
Function F001 setting – The value in F001 is a constant,
used for the output frequency
03
ModBus network input – The network has a dedicated
resister for inverter output frequency
10
Calculate function output – The Calculated function has
user-selectable analog input sources (A and B). the output
can be the sum, difference, or product (+, -, x) of the two
outputs.
ManualsBase.com
Description
Five options; select codes:
00 ...Keypad potentiometer
01 ...Control terminal
02 ...Function F001 setting
03 ...ModBus network input
10 ...Calculate function output
Three options; select codes:
01 ...Control terminal
02 ...Run key on keypad,
or digital operator
03 ... ModBus network input
Frequency Source
Defaults
Run
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
01
00
01
00
01
02
01
02
Refer to page(s)...
2-24
4-53, 3-13, 3-28,
3-49
3-9
B-19
3-29

Advertisement

Table of Contents
loading

Table of Contents