Monitoring Trip Events, History, & Conditions
Fault Detection and Clearing
The microprocessor in the inverter detects a variety
of fault conditions and captures the event,
recording it in a history table. The inverter output
turns OFF, or "trips" similar to the way a circuit
breaker trips due to an over-current condition.
Most faults occur when the motor is running (refer
to the diagram to the right). However, the inverter
could have an internal fault and trip in Stop Mode.
In either case, you can clear the fault by pressing the Stop/Reset key. Additionally, you
can clear the inverter's cumulative trip history by performing the procedure
Factory Default Settings" on page 6–8
leave inverter settings intact).
Error Codes
An error code will appear on the display automatically when a fault causes the inverter
to trip. The following table lists the cause associated with the error.
More user manuals on
Error
Name
Code
E 01
Over-current event while at
constant speed
E 02
Over-current event during
deceleration
E 03
Over-current event during
acceleration
E 04
Over-current event during
other conditions
E 05
Overload protection
E 07
Over-voltage protection
E 08
EEPROM error
E 09
Under-voltage error
E 11
CPU error
E 12
External trip
ManualsBase.com
Run
Fault
(setting B084=00 will clear the trip history but
Cause(s)
The inverter output was short-circuited, or the
motor shaft is locked or has a heavy load. These
conditions cause excessive current for the inverter,
so the inverter output is turned OFF.
The dual-voltage motor is wired incorrectly.
When a motor overload is detected by the electronic
thermal function, the inverter trips and turns OFF
its output.
When the DC bus voltage exceeds a threshold, due
to regenerative energy from the motor.
When the built-in EEPROM memory has problems
due to noise or excessive temperature, the inverter
trips and turns OFF its output to the motor.
A decrease of internal DC bus voltage below a
threshold results in a control circuit fault. This
condition can also generate excessive motor heat or
cause low torque. The inverter trips and turns OFF
its output.
A malfunction in the built-in CPU has occurred, so
the inverter trips and turns OFF its output to the
motor.
A signal on an intelligent input terminal configured
as EXT has occurred. The inverter trips and turns
OFF the output to the motor.