2-5-6 Wiring for Auto-reset (Interlock is Invalid)
(Wiring Example of the Control Category 4)
<In case of using I/O circuit for PNP output with SF4B-□C>
Gray cable
Gray cable
with black line
Interlock function
External device monitor function Valid
Auxiliary output
The device output is selected depending on the connecting state of the output polarity setting wire
(shield). Incorrect wiring may cause the lockout state.
* Symbols
Switch S1
Vs to Vs - 2.5V (sink current 5mA or less): Emission (Note), Open: Emission halt
K1, K2: External device (Forced guided relay or magnetic contactor)
Notes: 1) Vs is the applying supply voltage.
2) For resetting, refer to "3-2 Interlock Function."
© Panasonic Industrial Devices SUNX Co., Ltd. 2014
Ramco National
(Pale purple) Interlock setting input
(Brown) +V
(Pink) Emission halt input / Reset input
(Yellow-green / Black) Auxiliary output
(Shield) Output polarity setting wire
(Blue) 0V
(Orange) Synchronization +
(Orange / Black) Synchronization -
(Orange / Black) Synchronization -
(Orange) Synchronization +
(Yellow-green) External device monitor input
(Brown) +V
(Black) Control output 1 (OSSD 1)
(White) Control output 2 (OSSD 2)
(Shield) Output polarity setting wire
(Blue) 0V
Invalid (Auto-reset)
Can be used
800-280-6933 | nsales@ramcoi.com
*S1
+
Load
-
K1
K2
K1
K2
www.panasonicsensors.com
Wiring
24V DC
±10%
53