Chapter 4
[AJ-53]~[AJ-59]
Code/Name
AJ-53
PID4 proportional gain
AJ-54
PID4 integral time constant
AJ-55
PID4 derivative gain
・Sets the PID4 gain.
・If [PIDC] terminal is active (ON), the value of the
integral constant is purged. If done while operating, the
operation can become instable/insecure.
Code/Name
AJ-56
PID4 output range
PID output (%)
PID
Target
value
・Limits the output range of the PID. If [AJ-56]=0.00 the
limit is disabled.
Code/Name
AJ-57
PID4 deviation level
PID deviation (%)
0%
Output
terminal
ON
091[OD4]
・When the PID deviation pass over ±[AJ-57], the output
terminal function 091[OD4] is activated.
Code/Name
AJ-58
Maximum PID4 feedback
AJ-59
Minimum PID4 feedback
PID feedback (%)
0%
Operation
command
092[FBV4]
ON
・When the PID feedback cross over the [AJ-58] level, the
output terminal function 092[FBV4] is deactivated
(OFF). If it crosses under the [AJ-59] level, is activated
(ON).
Initial
Range (unit)
value
1.0
0.0~100.0
0.0~3600.0(s)
1.0
0.0
0.0~100.0(s)
Range (unit)
Initial value
0.00
0.00~100.00(%)
PID output range
[AJ-36]
[AJ-36
]
Time(s)
Range (unit)
Initial value
0.00~100.00(%)
3.00
[AJ-37]
[AJ-37]
ON
Time(s)
Range (unit)
Initial
value
100.00
0.00~100.00(%)
0.00~100.00(%)
0.00
[AJ-58]
[AJ-59]
Time(s)
ON
ON
For parameter configuration
■Parameter mode (b code)
Frequency limit
Code/Name
bA102
Frequency upper limit, 1st-motor
bA103
Frequency lower limit, 1st-motor
・Sets upper and lower limits of the frequency.

Torque limit

Code/Name
bA110
Torque limit selection, 1st-motor
bA111
Torque limiting
parameter selection, 1st-motor
bA112
Torque limit (1)
(forward-driving in 4-quadrant
mode), 1st-motor
bA113
Torque limit (2)
(reverse-regenerating in
4-quadrant mode), 1st-motor
bA114
Torque limit (3)
(reverse-driving in 4-quadrant
mode), 1st-motor
bA115
Torque limit (4)
(forward-regenerating in
4-quadrant mode), 1st-motor
bA116
Torque limit LADSTOP
enable, 1st-motor
*1) 01(Ai1 terminal)/02(Ai2 terminal)/03(Ai3 terminal)/07(Parameter)/
08(RS485)
・In the case of vector control (With sensor – Sensorless –
0Hz) the torque limit function can limit the motor
output torque.
4-28
[bA102]~[bA115]
Initial
Range (unit)
value
0.00~590.00(Hz)
0.00
0.00
0.00~590.00(Hz)
Range (unit)
Initial value
01~03/
27
07, 08 *1)
00(4 quadrants)/
00
01([TRQ] terminal)
0.0~500.0(%)
120.0(%)
0.0~500.0(%)
120.0(%)
120.0(%)
0.0~500.0(%)
0.0~500.0(%)
120.0(%)
00(Disable)/
00
01(Enable)