Removing Power Supplies - Cisco MDS 9132T Installation Manual

Fibre channel switch
Hide thumbs Also See for MDS 9132T:
Table of Contents

Advertisement

Installing the Cisco MDS 9132T Switch

Removing Power Supplies

You can remove one faulty power supply while the other one provides enough power to the switch. Install a
new power supply or a power supply blank module in the open slot.
Step 1
Holding the plug for the power cable, pull the plug out from the power receptacle on the power supply and verify that
both power supply LEDs are off.
Step 2
Grasp the power supply handle while pressing the release latch towards the power supply handle.
Step 3
Place your other hand under the power supply to support it while you slide it out of the chassis.
Do not touch the electrical connectors on the back side of the module and prevent anything else from coming
Caution
into contact with and damaging the connectors.
What to Do Next
Insert a power supply blank module as shown in
not have a new power supply unit.
Installing and Removing Fan Modules
This section provides instructions for installing and removing the fan modules for the Cisco MDS 9132T
switch.
You can replace one of the four fan modules at a time while the switch is operating so long as you perform
the replacement within one minute of removal of the old fan module. If you cannot perform the replacement
within one minute, leave the original fan module in the chassis to maintain the designed airflow until you
have the replacement fan module on hand and can perform the replacement.
If you are replacing a module during operations, be sure that the replacement fan module has the correct
Caution
direction of airflow, which means that it has the same airflow direction as the other modules in the chassis.
Also, be sure that the airflow direction takes in air from a cold aisle and exhausts to a hot aisle. Otherwise,
the switch can overheat and shutdown.
If you are changing the airflow direction of all the modules in the chassis, you must shutdown the switch
before replacing all the fan and power supply modules with modules using the other airflow direction.
During operations, all of the modules must have the same direction of airflow.
Installing a Fan Module
To install a new fan module, follow these steps:
Before You Begin
If a fan blank module is installed, remove it as follows:
1. Press the two sides of the fan blank module handle and pull on the handles enough to unseat it from its
connectors.
Figure 16: Inserted Power Supply Blank Module
Cisco MDS 9132T Fibre Channel Switch Hardware Installation Guide
Installing and Removing Fan Modules
if you do
39