B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 8 of 52)
ADDR
REGISTER NAME
255E
PMU 1 Ground Current Magnitude
2560
PMU 1 Ground Current Angle
2561
PMU 1 Positive Sequence Current Magnitude
2563
PMU 1 Positive Sequence Current Angle
2564
PMU 1 Negative Sequence Current Magnitude
B
2566
PMU 1 Negative Sequence Current Angle
2567
PMU 1 Zero Sequence Current Magnitude
2569
PMU 1 Zero Sequence Current Angle
256A
PMU 1 Frequency
256C
PMU 1 df/dt
256D
PMU 1 Configuration Change Counter
256E
Reserved (4 items)
2572
...Repeated for PMU 2
25A4
...Repeated for PMU 3
25D6
...Repeated for PMU 4
Phasor measurement unit integer values (read only actual value registers)
2608
PMU 1 SOC timestamp
260A
PMU 1 FRAMESEC timestamp
260C
PMU 1 STAT flags
260E
...Repeated for PMU 2
2614
...Repeated for PMU 3
261A
...Repeated for PMU 4
Remote double-point status inputs (read/write setting registers)
2620
Remote double-point status input 1 device
2621
Remote double-point status input 1 item
2622
Remote double-point status input 1 name
2628
Remote double-point status input 1 events
2629
... Repeated for double-point status input 2
2632
... Repeated for double-point status input 3
263B
... Repeated for double-point status input 4
2644
... Repeated for double-point status input 5
IEC 61850 GGIO5 configuration (read/write setting registers)
26B0
IEC 61850 GGIO5 uinteger input 1 operand
26B1
IEC 61850 GGIO5 uinteger input 2 operand
26B2
IEC 61850 GGIO5 uinteger input 3 operand
26B3
IEC 61850 GGIO5 uinteger input 4 operand
26B4
IEC 61850 GGIO5 uinteger input 5 operand
26B5
IEC 61850 GGIO5 uinteger input 6 operand
26B6
IEC 61850 GGIO5 uinteger input 7 operand
26B7
IEC 61850 GGIO5 uinteger input 8 operand
26B8
IEC 61850 GGIO5 uinteger input 9 operand
26B9
IEC 61850 GGIO5 uinteger input 10 operand
26BA
IEC 61850 GGIO5 uinteger input 11 operand
26BB
IEC 61850 GGIO5 uinteger input 12 operand
26BC
IEC 61850 GGIO5 uinteger input 13 operand
26BD
IEC 61850 GGIO5 uinteger input 14 operand
26BE
IEC 61850 GGIO5 uinteger input 15 operand
26BF
IEC 61850 GGIO5 uinteger input 16 operand
IEC 61850 received integers (read only actual values)
26F0
IEC 61850 received uinteger 1
26F2
IEC 61850 received uinteger 2
26F4
IEC 61850 received uinteger 3
26F6
IEC 61850 received uinteger 4
26F8
IEC 61850 received uinteger 5
B-16
RANGE
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
2 to 90
-327.67 to 327.67
0 to 655.35
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
1 to 32
0 to 128
1 to 64
0 to 1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
L30 Line Current Differential System
UNITS
STEP
FORMAT
A
0.001
F060
°
0.1
F002
A
0.001
F060
°
0.1
F002
A
0.001
F060
°
0.1
F002
A
0.001
F060
°
0.1
F002
Hz
0.001
F003
Hz/s
0.01
F002
0.01
F001
---
1
F001
seconds
1
F003
seconds
1
F003
---
1
F003
---
1
F001
---
1
F156
---
1
F205
---
1
F102
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
APPENDIX B
DEFAULT
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0 (None)
"Rem Ip 1"
0 (Disabled)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
GE Multilin