Battery Lives Of Cpu Modules - Mitsubishi Q01CPU User Manual

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

11
MAINTENANCE AND INSPECTION

11.3.2 Battery lives of CPU modules

(1) Battery (Q6BAT) lives of Basic model QCPUs
CPU module
Q00JCPU
Q00CPU
Q01CPU
Power-on time
model
*1
ratio
0%
30%
50%
70%
100%
0%
30%
50%
70%
100%
0%
30%
50%
70%
100%
* 1: The power-on time ratio indicates the ratio of programmable controller power-on time to one day
(24 hours).
(When the total power-on time is 12 hours and the total power-off time is 12 hours, the power-on
time ratio is 50%.)
* 2: The guaranteed battery service life; equivalent to the total power failure time that is calculated
based on the characteristics value of the memory (SRAM) supplied by the manufacturer and
under the storage ambient temperature range of -25 to 75
to 55
).
* 3: The actual battery service life; equivalent to the total power failure time that is calculated based on
the measured value and under the storage ambient temperature of 40
for reference only, as it varies with characteristics of the memory.
* 4: In the following status, the backup time after power OFF is 3 minutes.
•The battery connector is disconnected.
•The lead wire of the battery is broken.
Table11.5 Battery life
Battery life
Actual service
Guaranteed value
value (Reference
*2
(70
)
value)
26,000hr
2.96 years
5.00 years
37,142hr
4.23 years
5.00 years
43,800hr
5.00 years
5.00 years
43,800hr
5.00 years
5.00 years
43,800hr
5.00 years
5.00 years
26,000hr
2.96 years
5.00 years
37,142hr
4.23 years
5.00 years
43,800hr
5.00 years
5.00 years
43,800hr
5.00 years
5.00 years
43,800hr
5.00 years
5.00 years
5,600hr
0.63 years
2.87 years
8,000hr
0.91 years
4.10 years
11,200hr
1.27 years
5.00 years
18,666hr
2.13 years
5.00 years
43,800hr
5.00 years
5.00 years
11.3 Battery Life and Replacement Procedure
11.3.2 Battery lives of CPU modules
After SM52 turns
ON.(Power failure
compensation time
*3
(40
)
after alarm
43,800hr
710hr
30 days
43,800hr
710hr
30 days
43,800hr
710hr
30 days
43,800hr
710hr
30 days
43,800hr
710hr
30 days
43,800hr
710hr
30 days
43,800hr
710hr
30 days
43,800hr
710hr
30 days
43,800hr
710hr
30 days
43,800hr
710hr
30 days
25,175hr
420hr
18 days
35,964hr
420hr
18 days
43,800hr
420hr
18 days
43,800hr
420hr
18 days
43,800hr
420hr
18 days
(operating ambient temperature of 0
. This value is intended
11
9
10
*4
)
11
12
- 7