Last Trip Data; Fault Locations - GE 750 Instruction Manual

Feeder management relay
Hide thumbs Also See for 750:
Table of Contents

Advertisement

750/760
Feeder Management Relay

Last Trip Data

LAST TRIP DATA

Fault Locations

FAULT
LOCATION 0
6–6
PATH: ACTUAL VALUES
A1 STATUS
[ ]
DATE OF LAST TRIP:
Nov 17 2003
TIME OF LAST TRIP:
MESSAGE
12:34:56.789
TRIP: <Φ>
MESSAGE
<Cause>
A:
MESSAGE
C:
GND CURRENT:
MESSAGE
SENSTV GND CURRENT:
MESSAGE
NEUTRAL CURRENT:
MESSAGE
AN:
MESSAGE
CN:
AB:
MESSAGE
CA:
NEUTRAL VOLTAGE:
MESSAGE
SYSTEM FREQ:
MESSAGE
0.00 Hz
ANALOG INPUT:
MESSAGE
Independent of the event recorder, the relay captures the system information at the
time of the last trip event. This information includes a time and date stamp, trip
cause, phase current, ground current, sensitive ground current, neutral current,
voltages, system frequency, and the analog input. If more than one protection
element trips for a fault (for example, both the Phase and Neutral Instantaneous
Overcurrent 1 elements) then only the first trip event detected by the relay will have
Last Trip Data captured. This information cannot be cleared; data for a new trip
overwrites the previous trip data.
The AN, BN, and CN voltage values are seen only if the
SENSING
VT CONNECTION TYPE
are seen only if this setpoint is "Delta" or "None". The units for
by the
S6 MONITORING
ANALOG INPUT
PATH: ACTUAL VALUES
A1 STATUS
[ ]
DATE OF FAULT 0:
Nov 17 2003
TIME OF FAULT 0:
MESSAGE
12:34:56.789
TYPE OF FAULT:
MESSAGE
n/a
DISTANCE TO FAULT:
MESSAGE
Zpos (INDUCTIVE)
MESSAGE
OHM TO FAULT:
http://www.GEmultilin.com
LAST TRIP DATA
Range: Date in format shown
Range: Time in format shown
Range: See A4 Event Recorder on
Range: 0 to 65535 A
0
B:
0
0
Amps
Range: 0 to 65535 A
0 A
Range: 0 to 655.35 A
0.00 A
Range: 0 to 65535 A
0 A
Range: 0 to 65535 kV
0.00
BN:
0.00
0.00
kVolts
Range: 0 to 65535 kV
0.00
BC:
0.00
0.00
kVolts
Range: 0 to 655.35 kV
0.00 kV
Range: 0.00 to 65.00 Hz
Range: 0 to 65535 units.
0 μA
setting is "Wye". The AB, BC, and CA voltage values
ANALOG INPUT SETUP
FAULT LOCATIONS
Range: Date in format shown
Range: Time in format shown
Range: Phase A, Phase B, Phase C,
Range: –327.68 to 327.68 km/mi
0.00 km
Range: 0.00 to 655.35 Ω.
0.00
A1 Status
page 6–16.
S2 SYSTEM SETUP
BUS VT
are set
ANALOG INPUT
setting.
A/I UNITS
FAULT LOCATION 0(9)
Ground
GE Multilin