Sntp Protocol - GE 889 Instruction Manual

Generator protection system
Hide thumbs Also See for 889:
Table of Contents

Advertisement

DEVICE
IRIG-B
FASTPATH:

SNTP Protocol

FASTPATH:
4–12
IRIG-B is available in the basic offering of the product. A failure on IRIG-B triggers an event
and a target message.
Note that IRIG-B is auto detect. The signal type is detected in hardware, so there are no
configurable options.
Path:
Setpoints > Device > Real Time Clock > SNTP
SNTP FUNCTION
Range: Disabled, Enabled
Default: Disabled
SNTP SERVER IP ADDRESS
Range: Standard IP Address Format
Default: 0.0.0.0
SNTP UDP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 123
SNTP SERVER 2 IP ADDRESS
Range: Standard IP Address Format
Default: 0.0.0.0
SNTP 2 UDP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 123
The SNTP and PTP settings take effect after rebooting the relay.