GE D30 Instruction Manual page 170

Line distance
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5.4 FLEXLOGIC™
Table 5–5: D30 FLEXLOGIC™ OPERANDS (Sheet 5 of 6)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
SYNC 1 DEAD S OP
Synchrocheck
SYNC 1 DEAD S DPO
SYNC 1 SYNC OP
SYNC 1 SYNC DPO
SYNC 1 CLS OP
SYNC 1 CLS DPO
5
SYNC 1 V1 ABOVE MIN
SYNC 1 V1 BELOW MAX
SYNC 1 V2 ABOVE MIN
SYNC 1 V2 BELOW MAX
SYNC 2
ELEMENT:
TELEPRO CH1 FAIL
Teleprotection
TELEPRO CH2 FAIL
channel tests
TELEPRO CH1 ID FAIL
TELEPRO CH2 ID FAIL
TELEPRO CH1 CRC FAIL
TELEPRO CH2 CRC FAIL
TELEPRO CH1 PKT LOST
TELEPRO CH2 PKT LOST
ELEMENT:
TELEPRO INPUT 1-1 On
Teleprotection
inputs/outputs
TELEPRO INPUT 1-16 On
TELEPRO INPUT 2-1 On
TELEPRO INPUT 2-16 On
FIXED OPERANDS
Off
On
INPUTS/OUTPUTS:
Cont Ip 1
Contact inputs
Cont Ip 2
Cont Ip 1
Cont Ip 2
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
current
(from detector on
Cont Op 1
form-A output only)
Cont Op 2
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
voltage
(from detector on
Cont Op 1
form-A output only)
Cont Op 2
INPUTS/OUTPUTS
DIRECT INPUT 1 On
Direct inputs
DIRECT INPUT 32 On
INPUTS/OUTPUTS:
REMOTE INPUT 1 On
Remote inputs
REMOTE INPUT 32 On
INPUTS/OUTPUTS:
Virt Ip 1
Virtual inputs
Virt Ip 64
INPUTS/OUTPUTS:
Virt Op 1
Virtual outputs
Virt Op 96
LED TEST
LED TEST IN PROGRESS
REMOTE DEVICES
REMOTE DEVICE 1 On
REMOTE DEVICE 16 On
REMOTE DEVICE 1 Off
REMOTE DEVICE 16 Off
5-72
OPERAND DESCRIPTION
Synchrocheck 1 dead source has operated
Synchrocheck 1 dead source has dropped out
Synchrocheck 1 in synchronization has operated
Synchrocheck 1 in synchronization has dropped out
Synchrocheck 1 close has operated
Synchrocheck 1 close has dropped out
Synchrocheck 1 V1 is above the minimum live voltage
Synchrocheck 1 V1 is below the maximum dead voltage
Synchrocheck 1 V2 is above the minimum live voltage
Synchrocheck 1 V2 is below the maximum dead voltage
Same set of operands as shown for SYNC 1
Channel 1 failed
Channel 2 failed
The ID check for a peer relay on channel 1 has failed
The ID check for a peer relay on channel 2 has failed
CRC detected packet corruption on channel 1
CRC detected packet corruption on channel 2
CRC detected lost packet on channel 1
CRC detected lost packet on channel 2
Flag is set, Logic =1
Flag is set, Logic =1
Flag is set, Logic =1
Flag is set, Logic =1
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
On
(will not appear unless ordered)
On
(will not appear unless ordered)
Off
(will not appear unless ordered)
Off
(will not appear unless ordered)
IOn
(will not appear unless ordered)
IOn
(will not appear unless ordered)
IOff
(will not appear unless ordered)
IOff
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOff
(will not appear unless ordered)
VOff
(will not appear unless ordered)
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
An LED test has been initiated and has not finished.
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
D30 Line Distance Relay