Testing functionality by secondary injection
11.3.2.2
108
Verifying the settings by secondary injection
It is advised to connect the analog output channels of the function block OOSPPAM to the
internal disturbance recorder (and in particular to the function block A4RADR) in order
to perform a better analysis of the tests.
If the device is in test mode, the recording of the disturbances are enabled by the setting in
Main menu/Settings/IED Settings/Monitoring/Disturbance report/
DisturbanceReport/DRPRDRE:1: set the parameter OpModeTest to On.
1.
Check the Application Configuration: verify that hardware voltage and current
channels of the IED are properly connected to SMAI function blocks, and that the
proper analog outputs of SMAI's are connected to the analog inputs of the function
block OOSPPAM.
2.
Connect three-phase voltage channels of the test set to the appropriate IED terminals.
3.
Connect in parallel two groups of three-phase currents of the test set to the appropriate
IED terminals.
4.
Connect the appropriate trip output of the IED to the input channel of the test set that
monitors the trip.
5.
Go to Main menu/Settings/IED Settings/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1, and make sure that the function is
enabled, that is, Operation is set to On.
Test of point RE (R
FwdR
The trajectory of the impedance does not enter the lens characteristic.
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs to check the available
service values of the function block OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related to
phase L1):
V
VT s
,
V
1 1
.
V
=
×
×
ts
t FwdZ
,
V
VT p
,
EQUATION14057 V1 EN
ForwardX
=
V
arctan
ts
ForwardR
EQUATION14058 V1 EN
frequency of V
= 50 Hz
ts
, X
)
FwdX
0 1
.
1 1 11931
.
95 1
.
V
=
×
×
=
13 8
.
59 33
.
 =
 =
arctan
82. . 14°
8 19
.
1MRK 511 366-UUS -
(Equation 17)
(Equation 18)
Commissioning manual