2.4

Output Specifications

The CPU module output specifications are explained below.

Relay output

Item
No. of output points
Connection type
Output type
External power supply
Max. load
Min. load
Open circuit leakage current
Response time
Output circuit insulation
Indication of output operation
Output circuit configuration
2 SPECIFICATIONS
36
2.4 Output Specifications
Output Specifications
FX5U-32MR/
16 points
FX5U-64MR/
32 points
FX5U-80MR/
40 points
Removable terminal block (M3 screws)
Relay
30 V DC or less
240 V AC or less ("250 V AC or less" if not a CE, UL, cUL compliant item)
2 A/point
The total load current per common terminal should be the following value.
• 4 output points/common terminal: 8 A or less
• 8 output points/common terminal: 8 A or less
For details on the common, refer to Page 45 Interpretation of terminal block layout.
5 V DC, 2 mA (reference values)
OFF→ON
Approx. 10 ms
ON→OFF
Approx. 10 ms
Mechanical insulation
LED is lit when output is on
Load
DC power supply
Fuse
Load
AC power supply
Fuse
A number is entered in the of [COM ].
Y
COM
Y
COM