Appendix 4
This section describes precautions when the device is used at an operating ambient temperature below 0.
Precaution when used at an operating ambient temperature below 0
• With some exceptions, the operating ambient temperature is -20 to 55 for the FX5 PLCs manufactured in June 2016
onwards.
• The operating ambient temperature is 0 to 55 for the FX5 PLCs manufactured before June 2016.
• When the device is used in a low-temperature environment, use care not to let the product freeze or condensation to occur.
• When used in a low-temperature environment, use in an environment with no sudden temperature changes. If there are
sudden temperature changes because of opening/closing of the control panel or other reasons, condensation may occur,
which may cause a fire, fault, or malfunction. Furthermore, use an air conditioner in dehumidifier mode to prevent
condensation.
Related devices which cannot be used at an operating ambient temperature below 0
The following devices cannot be used at an operating ambient temperature below 0.
Device name
FX5-40SSC-S
FX5-80SSC-S
FX5-CNV-BUS
FX5-CNV-BUSC
Battery (FX3U-32BL)
SD memory card (NZ1MEM-2GBSD, NZ1MEM-4GBSD, NZ1MEM-8GBSD, NZ1MEM-16GBSD, L1MEM-2GBSD, L1MEM-4GBSD)
FX3 expansion module
Terminal module
Input/output cable (FX-16E-500CAB-S, FX-16E-CAB, FX-16E-CAB-R)
Specifications when used at an operating ambient temperature below 0
For using the device at an operating ambient temperature below 0, specifications are different from when used at an
operating ambient temperature of 0 to 55.
Item
Capacity of 24 V DC
service power supply of
the CPU module (AC
power supply type)
Built-in analog accuracy of the CPU module
Analog accuracy of FX5-4AD-ADP
APPX
186

Appendix 4 Precautions for Operating Ambient Temperature

Precautions for Operating Ambient
Temperature
FX5U-32M/E
Supply capacity when 24 V DC service power
supply is used for the input circuit of the CPU
module
Supply capacity when external power supply
is used for the input circuit of the CPU module
FX5U-64M/E
Supply capacity when 24 V DC service power
supply is used for the input circuit of the CPU
module
Supply capacity when external power supply
is used for the input circuit of the CPU module
FX5U-80M/E
Supply capacity when 24 V DC service power
supply is used for the input circuit of the CPU
module
Supply capacity when external power supply
is used for the input circuit of the CPU module
Analog input
Analog output
Analog input
When used at 0 to 55
When used at below 0
400 mA
300 mA
480 mA
380 mA
600 mA
300 mA
740 mA
440 mA
600 mA
300 mA
770 mA
470 mA
Within ±1.0% (±40 digit)
Within ±1.5% (±60 digit)
Within ±1.0% (±40 digit)
Within ±1.5% (±60 digit)
Within ±0.2% (±32 digit)
Within ±0.3% (±48 digit)