DNP DEVICE PROFILE
Object 20 (binary counters)
202
3 (select)
4 (operate)
5 (direct operate)
6 (direct operate, no acknowledge)
Qualifier codes for requests, object 12, variation 1:
00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
The following codes are used for responses.
Function codes for responses, object 12, variation 1:
129 (response)
Qualifier codes for responses, object 12, variation 1:
echo of request
Object 20, variation 0: Binary counter
Variation 0 is used to request the default variation. The following codes are used for
requests.
Function codes for requests, object 20, variation 0:
1 (read)
7 (freeze)
8 (freeze, no acknowledge)
9 (freeze clear)
10 (freeze clear, no acknowledge)
22 (assign class)
Qualifier codes for requests, object 20, variation 0:
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
There are no codes used for responses.
Object 20, variation 1: 32-bit binary counter
Object 20, variation 2: 16-bit binary counter
Object 20, variation 5: 32-bit binary counter without flag
Object 20, variation 6: 16-bit binary counter without flag
The following codes are used for requests.
Function codes for requests, object 20, variations 1, 2, 5, and 6:
1 (read)
7 (freeze)
8 (freeze, no acknowledge)
9 (freeze clear)
10 (freeze clear, no acknowledge)
22 (assign class)
Qualifier codes for requests, object 20, variations 1, 2, 5, and 6:
00, 01 (start-stop)
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 3: DNP COMMUNICATION