Environmental

Operating Temperature*
Operating Humidity
Storage Temperature*
Storage Humidity
NEMA Rating
UL Rating
Operational Vibration
Operational Shock
Rated temperature limits refer to the ambient air temperature immediately
surrounding (less than 3" or 7.6 cm) the QuickPanel inside the enclosure in which
the QuickPanel is mounted. Additional provisions for remaining within the stated
limits must be considered where additional, external thermal loads are imposed
on the QuickPanel. These could include large heat producing motor drives, or
power supplies in the same cabinet or in outdoor applications involving direct sun
exposure.

Battery

Type
Approximate
GFK-2327B
14°F to 140°F
(-10°C to 60°C)
10% to 85% non-condensing
-4 to 158°F
-20 to 70°C
10% to 85% non-condensing
4, 4x and 12
Applies to front of installed unit when mounted in a
comparably rated NEMA panel (NEMA 4 is
approximately equivalent to IP66; visit
www.nema.org)
Type 4X
Suitable for mounting on the flat surface of a type
4X enclosure.
IEC 60068-2-6
10–57Hz, 0.012" peak to peak displacement
57–500Hz, 1.0g acceleration
IEC 60068-2-27
15g, 11ms (sine wave)
BR2032 (3V, 190mAh, lithium)
5 years