Honeywell DT8035 DUAL TEC Quick Installation Manual page 2

Motion sensor

Advertisement

2
1. Apply power to the sensor. Initialization is complete when the LED stops
flashing slowly (about 30 seconds).
2. Turn the microwave sensitivity counterclockwise to reduce the microwave
range (minimum = 16.4' / 5m) and close the sensor.
3. Walk through the detection area and observe the LED.
4. Adjust the microwave range as necessary to meet installation requirements.
Walk test mode is active for 10 minutes, then automatically exits test mode, disables the LED and enters normal
operation mode. For an additional 10 minute walk test, enable walk test mode again with the flashlight feature (see Walk
Test Reset above).
Note: During power up and walk test modes the LED is active regardless of the LED Enable/Disable DIP switch setting.
Top View
Vue de dessus
Vista Desde Arriba
Vista Superior
PLAN VIEW
ALL ZONES
Tamper
30 mA
25 VDC
T
1
6
30 sec
0
10
45
20
30
33ft
(10m)
27ft
(8m)
20ft
(6m)
13ft
(4m)
7ft
(2m)
0ft
(0m)
7ft
(2m)
13ft
(4m)
20ft
(6m)
27ft
(8m)
33ft
(10m)
0ft
7ft
13ft
20ft
27ft
(0m)
(2m)
(4m)
(6m)
(8m)
Alarm
Power
30 mA
17 mA
25 VDC
9-15 VDC
(UL: 9.5-15 VDC)
-
+
T
C
NC
V
V
5
4
3
2 1
*
MIN
MAX
MW
SENSITIVITY
Side View
Vue de coté
Vista Lateral
Vista Lateral
Zones / Zones / Zonas / Zonas
A
18
B
46
C
36
D
33ft
40ft
(10m)
(12m)
- 2 -
Panel / Panneau / Panel / Controle
Zone
Zone
COM
#
T
T
6
5
Sensor / Détecteur / Sensor / Sensor
Walk Test Reset
< 4' (1.2m)
1/2 sec.
hold 4x
LED
Power Up
Walk Test
Slow
ON
Red
Blink
Alarm
ON
Yellow
OFF
Microwave
ON
Green
OFF
PIR
7ft
(2m)
(4m)
7.5ft
(2.3m)
0ft
(0m)
A
B
Look-down / Basses / Vista Zona 0 /
2
Vigilância inferior
Lower / Courtes / Cercana/ Mais baixas
Intermediate / Intermédiaires / Intermedia /
Intermédias
Long / Longues / Largo Alcance / Longo
alcance
Zone
Zone
Ground +12V
COM
#
-
+
C
NC
V
V
4
3
2 1
ON
Normal
Fault
ON
Fast
Alarm
Blink
ON
OFF
Microwave
ON
OFF
PIR
13ft
27ft
33ft
40ft
20ft
(10m)
(6m)
(8m)
(12m)
C
D

Advertisement

loading