GE UR Series B30 Instruction Manual page 142

Bus differential system
Hide thumbs Also See for UR Series B30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
5
The B30 supports the Distributed Network Protocol (DNP) version 3.0. The B30 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the B30 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the B30 at one time.
The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the
ting is set to "Enabled", the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).
The DNP Channels sub-menu is shown below.
PATH: SETTINGS
PRODUCT SETUP
 DNP CHANNELS
5-18
DNP ENERGY DEFAULT
MESSAGE
DEADBAND: 30000
DNP PF DEFAULT
MESSAGE
DEADBAND: 30000
DNP OTHER DEFAULT
MESSAGE
DEADBAND: 30000
DNP TIME SYNC IIN
MESSAGE
PERIOD: 1440 min
DNP MESSAGE FRAGMENT
MESSAGE
SIZE: 240
DNP OBJECT 1
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 2
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 20
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 21
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 22
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 23
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 30
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 32
MESSAGE
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED
MESSAGE
CONTROL POINTS: 0
DNP TCP CONNECTION
MESSAGE
TIMEOUT: 120 s

COMMUNICATIONS
DNP CHANNEL 1 PORT:
NETWORK
DNP CHANNEL 2 PORT:
MESSAGE
COM2 - RS485
B30 Bus Differential System
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 1 to 10080 min. in steps of 1
Range: 30 to 2048 in steps of 1
Range: 1, 2
Range: 1, 2
Range: 1, 2, 5, 6
Range: 1, 2, 9, 10
Range: 1, 2, 5, 6
Range: 1, 2, 5, 6
Range: 1, 2, 3, 4, 5
Range: 1, 2, 3, 4, 5, 7
Range: 0 to 32 in steps of 1
Range: 10 to 300 s in steps of 1

DNP PROTOCOL
DNP CHANNELS
Range: NONE, COM1 - RS485, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
Range: NONE, COM1 - RS485, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
5 SETTINGS
set-
IEC 60870-5-104 FUNCTION
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents