Error
Error and cause
code
[OPERATION ERROR]
• The number of setting data dealt with the
instruction exceeds the applicable range.
• The storage data and constant of the device
specified by the instruction exceeds the
applicable range.
• When writing to the host CPU shared memory,
the write prohibited area is specified for the write
destination address.
• The range of storage data of the device
specified by the instruction is duplicated.
• The device specified by the instruction exceeds
the range of the number of device points.
• The interrupt pointer No. specified by the
instruction exceeds the applicable range.
• A link direct device, intelligent function module
device, and cyclic transmission area device are
specified for both (S) and (D) with the BMOV
instruction.
• The target station's network No. specified by the
network dedicated instruction does not exist.
• There are no link direct devices (J\)
■Collateral information
• Common information: Program error location
• Individual information: -
4101
■Diagnostic timing
• When instruction executed
[OPERATION ERROR]
• Data stored in the file register specified by an
instruction exceeds the applicable range.
• A file register has not been set. Or the set file
register does not store a file.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[OPERATION ERROR]
• The block data that crosses over the boundary
between the internal user device and the
extended data register (D) or extended link
register is specified (including 32-bit binary, real
number (single precision, double precision),
indirect address, and control data).
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
378
Corrective action
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.