Enable standby local
HMI redirects to active
D400 procedure
Disable standby local
HMI redirects to active
D400 procedure
150
To enable Standby Local HMI redirects to Active D400:
1.
Log into the D400 Utilities page.
Result: The
D400 #>>
2.
Type d400cfg and press Enter.
Result: The D400 Configuration Utility menu appears.
3.
Select option 12. Local HMI.
Result: The Local HMI sub-menu appears.
4.
Select option 8. Standby Local HMI (Redundancy).
Result: The following prompt appears:
IMPORTANT !
* Currently Redundancy configuration is Disabled.
* Active D400 Access from Standby Local HMI configuration is
applicable only when Redundancy is Enabled.
* Number of simultaneous users must be a minimum of 2 for
the configured user role in both D400s, which can be
configured from HMI (Configuration > Systemwide >
AccessManager) menu.
Currently Active D400 Access from Standby Local HMI is
Disabled.
Are you sure you want to Enable Active D400 Access from
Standby Local HMI [Y/N]?:
5.
If you enter Y, then this feature is enabled.
If you enter N, then this feature is not enabled.
To disable Standby Local HMI redirects to Active D400:
1.
Log into the D400 Utilities page.
Result: The
D400 #>>
2.
Type d400cfg and press Enter.
Result: The D400 Configuration Utility menu appears.
3.
Select option 12. Local HMI.
Result: The Local HMI sub-menu appears.
4.
Select option 8. Standby Local HMI (Redundancy).
Result: The following prompt appears:
Currently Active D400 Access from Standby Local HMI is
Enabled.
Are you sure you want to Disable Active D400 Access from
Standby Local HMI [Y/N]?:
5.
If you enter Y, then this feature is disabled.
If you enter N, then this feature is not disabled.
GE INFORMATION
CHAPTER 12: USING THE D400 LOCAL CONFIGURATION UTILITY
command prompt appears.
command prompt appears.
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL