SECTION 4 (CONT'D}-Four-wire Ground Fault
4.3-Breaker Conversion-
AK/AKS-50 Stationary
The 4th-wire disconnect for stationary breakers is a terminal
board which is mounted to the lower front channel as shown
in Fig. 4-2.
If the terminal board already exists, just replace the
1.
control harness. Maintain the following color code:
WHITE-COMMON
BLACK-TAP
2. If the terminal board assembly is being added, mount
as shown in Fig. 4-2. The mounting holes may have to be
added to the front channel. See Fig. 4-2.
(DIMENSIONS IN INCHES)
Fig. 4-2. 4th-wire terminal board installed- AK/AKS-50 stationary
14
4.4-Breaker Conversion­
There are two 4th-wire disconnect designs used with these
breakers. One design is used on breakers for AKD Type
equipment. The other design is used on breakers for AKD-5/6
Type equipment. The difference in the designs is the bracket
used for mounting the disconnect to the breaker. Figure 4-3
depicts the two designs.
The Conversion Kits are shipped with the AKD-5/6 Type
assembled with only the bracket for the AKD Type. If an AKD
Type is required, remove the AKD-5/6 Type bracket and
replace it with AKD Type bracket.
TERMINAL
BOARD
ASSEMBLY
MOUNTING
HARDWARE
DRILL (2)
0 . 219 DIAMETER
HOLES
AK/AKR-75/100 Drawout
FRONT VIEW