All parameters
No.
Name/Value
SAVE...
1608 START
ENABLE 1
NOT SEL
DI1
DI2
DI3
DI4
DI5
Description
Saving in progress
Selects the source for the Start enable 1 signal.
Note: Functionality of the Start enable signal is different
from the Run enable signal.
Example: External damper control application using Start
enable and Run enable. Motor can start only after the
damper is fully open.
Drive started
Relay energized
Relay
de-
energized
Damper
closed
Damper
opening
time
Motor
speed
Start enable signal is on.
External signal required through digital input DI1. 1 = Start
enable. If Start enable signal is switched off, the drive will
not start or it coasts to stop if it is running and alarm
ENABLE 1 MISSING
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Actual signals and parameters 207
Damper open
Damper
closed
Damper
closing
time
from the damper end
Acceleration
Deceleration
time (2202)
time (2203)
(2021) is activated
Def/FbEq
1
NOT SEL
Start/Stop
command
(group 10)
Start enable
signals
(1608
and 1609)
Started
output status
(group 14)
Damper
status
Run enable signal
switch when the
damper is fully
opened. (1601)
Motor
status
0
1
START
2
3
4
5