HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
Cable Preparation
NOTE: This section will typically be used for reference
only. The S70X/S80X connector parts are very
small and delicate and difficult to assemble. It is
advisable to purchase pre-made cables from
Honeywell.
Honeywell C330S cable is recommended for use with the
S70X/S80X viewing heads and signal processors. C330S has
a UL ITC rating and can be used in the U.S. in hazardous
locations.
66-2069EP—04
CONDUIT
ENCLOSURE
Fig. 3. Model 700 Viewing Head Cable With 1/2 in. NPT Fitting.
VH SC
VIEWING HEAD
5/16 (8)
CONNECTOR
MAX
LOOKING AT PINS
C330S YELLOW, 4 COND
WITH FOIL/BRAID SHIELD
AND DRAIN (ITC & CIC)
Fig. 4. Model 700/800 Viewing Head Cable Connections.
S702PF OR S706PF
STANDARD "PIGTAIL" LENGTH = 10 FEET (3 METERS)
C330S YELLOW 4-CONDUCTOR
WITH DRAIN AND SHIELD
WHITE
BLACK
RED
GREEN
SHIELD
GREEN
VH SIG
LED
VH +V
VH GND
METAL
CONNECTOR
RING
CONNECTOR REAR VIEW
WITH NUT LOOSENED
AND COVER REMOVED
WHITE
BLACK
RED
SHIELD
GREEN
NOTE: Shield shrink tubing is required on shield drain
wire at the signal processor end.
Preparation of the C330S cable at the signal processor should
be done as follows:
1. Referring to Fig. 5, strip cable 2 inches back to expose
the braided shield.
2. Pull braided and foil shield back so that only drain wire
is at 2 inch length. Trim the foil and braid shields at the
cable jacket.
3. Insulate the drain wire with heat shrink.
4. Strip other wires as shown in Fig. 5.
8
TERMINAL
VH SIG
VH SC
VH +V
VH GND
M34285C
ORANGE
LED
TERMINAL
VH SIG
VH SC
VH +V
VH GND
M34286B