Panasonic 1828 Specification Sheet
Panasonic 1828 Specification Sheet

Panasonic 1828 Specification Sheet

Fire alarm systems external fire brigade panel

Advertisement

Quick Links

Control (key required) and indicating panel for the fire brigade personnel, etc.
Compact size
Ext. Fire Brigade Panel
This unit (S/W V1.2) is primarily intended
to be used by the fire brigade personnel, i.e.
for pre-warning, co-incidence, fire and
heavy smoke / heat alarm presentation.
Point or zone alarm presentation and fire
alarm reset are as in the c.i.e. it is connected
to. You can scroll amongst two or more
alarms in the system. All or selected alarms
will be presented in a display (LCD, 2x40
characters with back-light). An alarm text
will be presented together with each alarm,
if programmed in the c.i.e.
>617 texts for selected alarms can be stored
in the unit and will in such a case be shown,
instead of the texts sent from the c.i.e. for
these alarms. A built-in buzzer will sound
like in the c.i.e. Any fault in the system will
be presented as "General fault in system"
and the buzzer will sound.
power supplied via the c.i.e. or ext. power
supply.
LEDs, push buttons etc.
The unit has the following LEDs:
Fire and Alarms queued, indicating
pre-warning, co-incidence, fire and
heavy smoke / heat alarm
Operation, indicating that the unit is
connected to a c.i.e. and power
supplied, i.e. it is in operation.
Extinguishing,
indicating
output for Extinguishing equipment.
Ventilation, indicating activated output
for Ventilation equipment.
Fire brigade tx, indicating activated
output for Fire brigade tx (routing
equipm.).
Panasonic Electric Works Fire & Security Technology Europe AB
Citadellsvägen 23, SE-211 18 Malmö, Sweden
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Fire alarm systems
External Fire Brigade
The unit has the following push buttons:
The designation texts on the front are in
1828SE in Swedish but a neutral front for
Furthermore,
other languages is available (1828CC).
Compact size
The compact size enclosure is made of grey
high impact ABS.
mentary "O" ring gasket, it will comply with
IP61, in respect of dust and moisture. A key
The unit is
is required to get access to the push buttons
and they are disabled until they are supposed
to be used. A key is not required for the
alarm presentation and to silence the buzzer.
Two compression glands are attached. The
unit shall be wall mounted.
SW mode and address setting
The display and the push buttons are used to
set the SW mode and address, see the
opposite side of this page.
Product application
activated
The 1828 unit is intended for indoor use and
in dry premises. SW mode 1826/28 - 1587
is intended to be used in the systems
EBL512 and EBL128 SW mode 1826/28 –
1582 in the systems EBL500 / 512 / 1000 /
2000.
Panel 1828
Alarms queued, used to scroll amongst
the alarms.
Silence buzzer, used to silence the
buzzer (it will re-sound for a new
alarm.
Silence alarm devices, used to silence
the alarm devices (they will re-sound
for a new alarm.
Reset, used to reset the fire alarms.
Fitted with a supple-

Advertisement

loading

Summary of Contents for Panasonic 1828

  • Page 1 Product application activated The 1828 unit is intended for indoor use and in dry premises. SW mode 1826/28 - 1587 is intended to be used in the systems EBL512 and EBL128 SW mode 1826/28 –...
  • Page 2: Technical Data

    On each 1582 board are up to eight addresses available and on each 1587 board up to sixteen addresses. In EBL128 are up to four addresses available. Note! The alarm presentation will be as in the c.i.e. that ext. FBP is connected to, not as in 2425 / 2426. The 1828 front does not hold any LED "Zone/Detector not reset".