Honeywell Excel 50 User Manual page 40

Hide thumbs Also See for Excel 50:
Table of Contents

Advertisement

EN2B-0137GE51 R0216
Modem Config.
Baudrate:<
bdrate
GSM PIN:********
Reset Modm ›NEXT
NOTE: GSM communication is not supported.
Using the arrow keys, move the cursor to the value field. Confirm with ENTER.
NOTE: Changing the baud rates requires a level-2 password.
Change the values using the '+' or '–' keys. Confirm with ENTER.
Using the arrow keys, move the cursor to 'Reset Modem' to reset the modem to its
factory setting (insure that the modem is connected). Confirm with ENTER.
IMPORTANT
Resetting the modem will restore the factory defaults and erase any custom
initialization.
Using the arrow keys, move the cursor to 'NEXT' and confirm with ENTER.
Appl. Mem. Size
128 KB
Rem. Trend Buf.
104 Entr.
This screen displays the size of the adjustable remote trend buffer. The number of
entries (trend samples) that can be stored in the buffer for Remote Building Central
A is determined by a calculation by the controller based upon the Application
Memory Size entered in the start-up sequence. The values shown can be changed
only by resetting the controller and entering a new value for Appl. Mem. Size in the
start-up sequence.
NOTE: Firmware V2.03.01 or later and CARE V2.02.00 or later enables the con-
troller to run RACL partly from the Flash EPROM. Thus, the application
memory calculation is different compared to older versions. This has to be
considered during start up once you enter the application memory size.
1.
CARE V2.02.00 or later:
The maximum application size is 128 Kbytes (128 Kbytes flash
memory). Enter the application size calculated by CARE.
2.
CARE versions before V2.02.00 without modem:
The maximum application size calculated by the old CARE is 113
Kbytes because the complete application including RACL runs from
the RAM. The controller will not run if the application is bigger. You
need to use CARE at least V2.02.00 if your applications require more
than 113 Kbytes.
Applications bigger than 113 Kbytes without modem will not run
from the flash memory after firmware download of OS V2.03.01 if
they were done with CARE versions before V2.02.00.
3.
CARE versions before V2.02.00 with modem:
The maximum application size calculated by the old CARE is 100
Kbytes. The controller will not run if the application is bigger. For the
calculation of the trend buffer you need to enter 28 Kbytes plus the
application size calculated by the old CARE version, e.g., CARE
before V2.02.00 calculated 98 Kbytes, thus you will enter 126 Kbytes
(98 Kbytes + 28 Kbytes) on the MMI of the controller.
We strongly recommend using CARE V2.02.00 or later if you use
modem communication. This will allow for applications with up to 128
Kbytes (128 Kbytes flash memory).
Applications bigger than 100 Kbytes with modem will not run
from the flash memory after firmware download of OS V2.03.01 if
they were done with CARE versions before V2.02.00.
40
EXCEL 50 - USER GUIDE
This screen appears only when
>
modem communication is enabled.
This screen appears only when
modem communication is enabled.
›BACK