Honeywell Intelliguard 9000 Installation Instructions Manual page 20

Hide thumbs Also See for Intelliguard 9000:
Table of Contents

Advertisement

INTELLIGUARD 9000™
See Fig. 19 for installation instructions and Fig. 20 through 22 for detailed wiring and switch settings. The configuration in Fig. 20
can only be used for remote programming with a PC.
INTELLIGUARD
CONTROL
PANEL
1
INSTALL THE RRI IN THE TRACK SO THAT
SWITCH S1 POINTS OUTWARDS.
TOP OR
LEFT SIDE
PLASTIC
TRACK
7003-217
P.C.B.
BOTTOM OR
RIGHT SIDE
INTELLIGUARD ENCLOSURE
FRONT VIEW LOOKING INTO THE ENCLOSURE
RS-485 - BIAS AND TERMINATION
= DON'T CARE
DISABLE
BIAS
ENABLE
DISABLE
E.O.L.R.
TERMINATION
ENABLE
1
INSTALL THE RRI USING THE PLASTIC TRACK (INCLUDED).
SECURELY MOUNT PLASTIC TRACK TO INSIDE OF ENCLOSURE.
2
150 OHMS, 68,000 PF MAXIMUM.
NOTES:
– ONLY USE THIS WIRING CONFIGURATION FOR REMOTE
PROGRAMMING WITH A PC. ONE I9000 CU AT A TIME. THE I9000 TO
BE PROGRAMMED MUST BE DISCONNECTED FROM THE RS-485
NETWORK AND A LAP TOP PC CONNECTED TO THE I9000 PANEL AS
SHOWN ABOVE.
– FOR REMOTE PROGRAMMING, THE PC CAN BE CONNECTED
DIRECTLY TO THE I9000 CONTROL PANEL USING AN RS-232 LINK AS SHOWN IN THE I9000 CU WITH ICP II, ISP WIRING DIAGRAM, IN
THE CONTROL UNIT SECTION.
– THE GROUND BETWEEN UNITS 1 (TB2-1) AND 2 (TB2-1) ARE NOT NECESSARY IF A GROUND REFERENCE IS PROVIDED THROUGH
OTHER MEANS. (THIS IS TO PREVENT GROUND LOOPS.)
– SET THE SWITCHES OF RRI UNIT 1 FOR BIAS DISABLED (S1-1/S1-4 OFF) AND EOLR TERMINATION ENABLED (S1-2/S1-3 ON).
– SET THE SWITCHES OF RRI UNIT 2 FOR BIAS ENABLED (S1-1/S1-4 ON) AND EOLR TERMINATION ENABLED (S1-2/S1-3 ON).
– THE TRACK MAY BE SUSPENDED FROM THE TOP EDGE OF THE INTELLIGUARD ENCLOSURE OR INSTALLED ON THE RIGHT SIDE
WHEN ONLY ONE BATTERY IS REQUIRED. SEE RRI MOUNTING LOCATIONS DIAGRAM.
74-3047—1
S1
RST
COMM1 COMM2
DS2
DS4
DS1
INTELLIGENT
COMMUNICATIONS
XA2
PROCESSOR II
(ICP II)
8003-331
1 2 3 4 5 6 7 8 TB1
RETAINING
CLIP
TB1
1041-004
TB2
S1
4
3
2
1
POSITION
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Fig. 20. Pseudo RS-232 to RS-485 Interface 8003-321 installation.
XA1
XA4
U1
COM 3
DS3
1 2 3 4 5 6
RS-232
TB1
3 2 1
U1
U2
S1
4
3
2
1
ON
PSEUDO
RS-232 TO
RS-485
TB2
1 2 3 4
INTERFACE
(RRI)
8003-322
UNIT 1
2
PSEUDO
RS-232 TO
RS-485
4
3
2
1
TB2
INTERFACE
(RRI)
8003-322
ON
4
1
2
3
S1
U2
U1
1 2 3 TB1
UNIT 2
5
DE-9
3
2
DB-25
3
2
7
LAP TOP PC RS-232 PORT
RUNNING PRO 9000
SOFTWARE (8950-102)
20
XA3
TB2
PRODUCT IDENTIFICATION
LABEL
S1
4
3
2
1
LEVER
ON
M14464A