INTELLIGUARD 9000™
MOUNT MOM
To mount the MOM:
1. At the selected mounting location, remove the MOM
cover.
2. Use a No. 1 Robertson (square drive) screwdriver to
remove the screws securing the circuit board to the
back casing.
IMPORTANT
Touch a grounded object to ensure you are not elec-
trostatically charged before handling the circuit
board.
3. Gently remove the circuit board. Be sure not to touch
any of the circuits or terminals.
4. Mount the MOM on the wall using four No. 6 round or
pan head screws.
NOTE: Feed the required cables into the MOM base using
the two square holes in the base wiring channel, or
remove the knockouts on either end of the wiring
channel and pass the cables through the openings.
5. Replace the circuit board.
6. Connect the wires to the MOM as shown in Fig. 14.
7. Repeat steps 1 through 6 for each MOM.
8. When installation is complete and power is applied,
learn the MOM.
NOTE: Steps 8a. through 8k. may be replaced by using the
PRO 9000 software. See the Commission section,
steps 1a. through 1c. for more information.
a. Make sure the LED DS1 on each installed MOM dis-
plays C .
b. From each MOM, press the S2 switch (ACCEPT)
button to place each MOM in the COMMUNICA-
TION STATUS display mode.
c. The center segment (RECEIVE) of the LED display
(DS1) flashes to indicate incoming data.
d. The decimal point on the LED display (DS1) of each
MOM is off.
e. From the CC2 Mode menu, select 1-CONFIG to
enter the CONFIGURATION menu.
f.
From the CC2, select 1-LEARN to enter the
LEARNING menu.
g. From the CC2, select 2-DEVICES WITH SERIAL #
to start the learning process. The CC2 displays
Searching. The decimal point on the LED display
(DS1) lights on each MOM to indicate that the
MOMs are in the learning mode.
h. From each MOM, press and hold the S2 (ACCEPT)
button for approximately two seconds, or until the
bottom segment (TRANSMIT) of the LED display
DS1 flashes and the decimal point turns off. When
the decimal point disappears, the device is learned.
NOTE: If the MOM was previously learned, the decimal point
would have turned on and off almost immediately.
i.
When the ACCEPT key is pressed on the CC2, the
I9000 exits the learning mode and displays the total
number of devices known by the system including
the MOMs.
j.
From the CC2, exit the CONFIGURATION menu for
changes to become effective.
74-3047—1
k. The bottom segment (TRANSMIT) of the LED dis-
play (DS1) on each MOM flashes every time each is
polled (addressed). The center segment (RECEIVE)
also flashes.
9. Configure each output in the MOM, as needed. See
Output Parameters and Programming section.
10. Cause an alarm on the input that is linked to the corre-
sponding output to be tested. If a Hold-up Actuator was
pressed during the test, a RESET DETECTORS com-
mand is required to clear the latched alarm. (The out-
puts may only be tested when the I9000 programming is
completed).
11. Repeat steps 1 through 10 for each MOM.
12. Replace each MOM cover.
OUTPUT PARAMETERS AND PROGRAMMING
The MOM has nine programmable parameters:
Parameter 0 = Display
— 0 =Display is not active when tamper is closed.
— 1 = Display remains active when tamper is closed.
Parameters 1 to 8 = Outputs 1 to 8 respectively
Each output can be configured for one of three different types:
— 0 = Output is normally off, output turns on when activated.
— 1 = Output is normally on, output turns off when activated.
— 2 = Output is normally off and begins pulsating when
activated.
Programming
1. Press S3 (QUIT) to return to C on the LED display.
2. Press S1 (NEXT) until the LED display flashes P .
3. Press S2 to accept program mode.
4. Press S1 to scroll through the parameters to output 1.
No decimal point is displayed.
5. Press S2 to begin programming for output 1. A decimal
point appears in the bottom right corner of the LED dis-
play to indicate the present output type number.
6. Press S1 to scroll to the desired output type number (if
different from output type number displayed in step 5).
7. Press S2 to accept the displayed output type and to dis-
play the next parameter number.
8. Repeat steps 4. through 7. for each output.
9. Press S3 to leave the program mode.
COMMUNICATION AND OUTPUT FUNCTION STATUS DISPLAY
The MOM has three display modes:
— P allows the user to configure the individual outputs.
— C enters the Communication Display mode and causes the
center bar (RECEIVE) on the LED display to light each
time the MOM receives communication with the CU. The
bar closest to the terminal (TRANSMIT) lights whenever
the MOM responds.
— A enters the Output Function Status Display mode. The
number of the active output functions is displayed. If more
than one output is active, the display scrolls and shows
each active output for one second. When there are no
active outputs, the center bar on the seven segment LED
lights.
Other Detection Devices and Outputs
I9000 accepts connections to detection and warning devices
not included with the system; however, these devices must
conform to the requirements found in form no. 74-3035,
14