Wiring - Honeywell PRO TH3110D Installation Manual

Non-programmable digital thermostat for cool & heat
Hide thumbs Also See for PRO TH3110D:
Table of Contents

Advertisement

Available languages

Available languages

Installation Guide

Wiring

Wiring guide — conventional and heat pump systems
2H/1C Heat
Pump System
TH3210D
C
24 Vac common [3]
B
Changeover valve energized in
heating
[5]
R
Power
[1]
L
Sends output when set to Em. Heat [8]
O
Changeover valve energized in
cooling
[5]
G
Fan relay
Y
Compressor contactor
Aux
Auxiliary heat relay [9]
E
Emergency heat relay [9]
1H/1C System
TH3110D
(1 transformer)
C
24 Vac common [3]
R
[R+Rc joined by jumper]
Rc
Power
[1]
G
Fan relay
Y
Compressor contactor
W
Heat relay
1H/1C System
TH3110D
(2 transformers)
C
24 Vac common [3, 4]
R
Power (heating transformer) [1, 2]
Rc
Power (cooling transformer) [1, 2]
G
Fan relay
Y
Compressor contactor
W
Heat relay
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
[1] Power supply. Provide disconnect means
and overload protection as required.
[2]
Remove jumper for 2-transformer sys-
tems.
[3] Optional 24 Vac common connection.
[4] Common connection must come from
cooling transformer.
[5] Use either O or B terminals for changeover
valve.
69-1929EFS—01
Aux
Y
G
O
L
R
B
M29393
W
Y
G
O
Rc
R
B
MCR29394
W
Y
G
O
Rc
R
B
MCR29395
See
[notes]
below
1H/1C Heat
Pump System
C
TH3110D
[7]
C
24 Vac common [3]
B
Changeover valve energized in
heating [5]
R
[R+Rc joined by jumper]
Rc
Power
O
Changeover valve energized in
cooling
G
Fan relay
Y
Compressor contactor
W
[W+Y joined by jumper]
Heat Only
System
TH3110D
C
C
24 Vac common
R
[R+Rc joined by jumper]
Rc
Power
W
Heat relay
Heat Only
System with
Fan TH3110D
C
24 Vac common [3]
C
R
[R+Rc joined by jumper]
Power
Rc
G
Fan relay
W
Heat relay
Cool Only
System
TH3110D
C
24 Vac common [3]
R
[R+Rc joined by jumper]
Rc
Power
G
Fan relay
Y
Compressor contactor
[6] Use a small piece of wire (not supplied) to
connect W and Y terminals.
[7] Set fan operation switch to Heat Pump
(see page 5) and configure system type
for heat pump (see page 6).
[8]
L terminal sends a continuous output
when thermostat is set to Em. Heat.
Connect to Honeywell zoning panels to
switch the panel to Emergency Heat.
[9] Install field jumper between Aux and E if
there is no emergency heat relay.
4
W
Y
G
O
Rc
[1]
[5]
[6]
W
Rc
O
[3]
[1]
W
G
O
Rc
[1]
Y
G
O
Rc
[1]
R
B
C
MCR29396
R
C
B
MCR29397
R
B
C
MCR29398
R
B
C
MCR29399