BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
INTEGRATION
Global Commands
The following figure shows which objects from the thermostat can be monitored and commanded from the BAS front-end.
GLOBAL COMMANDS ALL DEVICES
(ALL THERMOSTATS)
OUTDOOR TEMPERATURE AND HVAC PLANT CURRENT MODE
GLOBAL COMMANDS SPECIFIC DEVICES
(SPECIFIC AREA THERMOSTATS)
ROOM TEMPERATURE FOR TESTING AND OVERRIDE
REMOTE CONTROL OF THE AUXILIARY OUTPUT
GLOBAL COMMAND CONTROL LEVEL
Fig. 6. Global commands from a BAS front-end to a typical TB7300 Series thermostat.
63-4524—03
OUTDOOR TEMPERATURE
SCHEDULE
SCHEDULE AND OUTDOOR TEMPERATURE
RESTRICT USER ACCESS TO THERMOSTAT
BAS FRONT-END
OUTDOOR TEMPERATURE (AV9)
SEQUENCE OF OPERATION (MV15)
SYSTEM MODE (AV16)
OCCUPANCY (MV18)
FAN MODE (MV17)
OCCUPIED HEATING SETPOINT (AV39)
UNOCCUPIED HEATING SETPOINT (AV43)
OCCUPIED COOLING SETPOINT (AV40)
UNOCCUPIED COOLING SETPOINT (AV44)
KEYPAD LOCKOUT (MV19)
ROOM TEMPERATURE (AV7)
AUX OUTPUT (BV14)
MSTP NETWORK
TB7300 SERIES TSTAT