Honeywell TB7200 Series Integration Manual page 19

Table of Contents

Advertisement

Standard Object Types Supported
Supported
Object Type
Analog Input
Analog Value
Binary Input
Binary Value
Device
Group
Multi-state Value
a
Present_Value and Out_of_Service properties are writable for every AV objects except :
• PI Heating Demand (AV21)
• PI Cooling Demand (AV22)
b
Present_Value property for Room Temperature (AV7) is writable only if Room Temp Override (BV8) is enabled.
c
Object_Name property is writable for the following object only :
• Room Temperature (AV7)
d
Present_Value and Out_of_Service properties are writable for every MV objects except :
• Heating Valve Status (MV26)
• Cooling Valve Status (MV27)
• Fan Status (MV28)
• Effective Occupancy (MV33)
List of Proprietary Properties
Property name
Major_Version
MS/TP_Address
MS/TP_Baud_Rate
Sensor_Offset
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
Table 6. Standard object types supported.
Dynamically
Objects
Creatable
Table 7. Proprietary Properties.
ID
BACnet Data type
1000
CharacterString
1001
Unsigned
1002
Unsigned
1005
REAL
Optional
Dynamically
Properties
Deletable
Supported
Reliability
Reliability
Reliability
Active_Text
Inactive_Text
Reliability
Active_Text
Inactive_Text
Max_Master
Max_Info_frames
N/A
Reliability
States_Text
Description
The version number of the BACnet communications
module. This is the hardware version number
Display the MAC layer address of the module
Display the communication baud rate of the module
Display the temperature calibration value.
The temperature range is –5.0 ºF to 5.0 ºF.
19
Writable Properties
Out_of_Service
a,b
Present_Value
a
Out_of_Service
c
Object_Name
Out_of_Service
Present_Value
Out_of_Service
Object_Identifier
Object_name
Max_Master
N/A
d
Present_Value
d
Out_of_Service
63-4524—03