Honeywell TB7200 Series Integration Manual page 23

Table of Contents

Advertisement

MV17 Index
Function MV58 State Text Index
1
1 Low - 2 Med - 3 High
2
1 Low - 2 High
3
1 Low - 2 Med - 3 High - 4 Auto
4
1 Low - 2 High - 3 Auto
5
1 Auto -2 On
Object Name
Heating Valve Status
Note 6
Cooling Valve Status
Note 8
Fan Status
Effective Occupancy
6.
Enumeration sets for MV26 depends on Control Type (BV75) value and Pipe Number (MV52) value upon device dis-
covery. If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV26 object.
Available enumeration will now reflect required configuration.
7.
Available object name, state text and default value depends on Control Type (BV75) value and Pipe Number (MV52)
upon device discovery.
BV75 Value
MV52 Index
On/Off
1 (2 pipe)
2 (4 pipe)
Floating
1 (2 pipe)
2 (4 pipe)
8.
Enumeration sets for MV27 depends on Control Type (BV75) value and Pipe Number (MV52) value upon device dis-
covery. If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV27 object.
Available enumeration will now reflect required configuration.
9.
Available object name, state text and default value depends on Control Type (BV75) value and Pipe Number (MV52)
upon device discovery.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
Table 10. Property enumeration sets for MV objects. (Continued)
Object ID
BACnet Index
MV 26
Note 7
MV 27
Note 9
1
2
MV 28
3
4
1
2
MV 33
3
4
MV26 Object
Name
Unused Output
Heating Valve
Status
Unused Output
Heating Valve
Status
Default Value
High
High
High
High
Auto
Text
Note 7
Note 9
Off
Low
Med
High
Occupied
Unoccupied
Temporary Occupied
Stand-by
Function MV26 State Text Index
N/A
1 Closed – 2 Open
N/A
1 Stopped - 2 Opening - 3 Closing
23
Default value
Note 7
Note 9
Off
Depends on local
occupancy
Default Value
N/A
Closed
N/A
Stopped
63-4524—03