12.5.2 Battery Charging

The UPS Solution offers temperature compensated battery charging to help keep all
battery packs in optimum condition across its extended operating ambient temperature
range. The battery charging voltage is adjusted by -5.0mV/°C/cell.

12.5.3 Battery Support Hold Up Times

Ambient temperature plays a big part in determining how much a battery support hold up
time is available. As temperature decreases, the available capacity of each battery pack
is reduced as battery chemistry becomes increasingly inert. This becomes very apparent
and extremely low ambient temperatures.
APPENDIX A – Estimated Hold Up Times shows battery hold up runtime charts (such as
in section 5) adjusted for ambient cabinet temperatures of +20°C, 0°C and -25°C.

12.6 Generators

12.6.1 The Generator Connect Feeder Pillar

As stated in section 2.4, a diesel generator must be connected via the Siemens
Generator Connect Feeder Pillar as shown below.
This feeder pillar variant incorporates a lockable cable entry point, a 2P+E
appliance inlet connector and a 63A double-pole changeover switch for isolation and
source selection.
Detailed information on the Generator Connect Feeder Pillar is available in the Isolators
and Feeder Pillar General Handbook – 667/HB/45040/000.
8
Two Pole and Earth
Version
7
Last Editor
Ore Oluwatudimu
Document
UPS Solution General Handbook
Name
Copyright ã Siemens plc 2017 All Rights Reserved
Figure 12-5: Generator Connect Feeder Pillar
Page 54 of 76
TS008468
Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
8
Status
ISSUED
Date
31/01/2017
Doc. No.
667/HB/47750/000
BH17 7ER
IP44 rated

Advertisement

Table of Contents
loading

Table of Contents