GE FVP110 Maintenance Manual page 206

Table of Contents

Advertisement

GE Energy
Relative
Index
Parameter
Index
18
2018
SERVO_
GAIN (*1)
19
2019
SERVO_
RESET (*1)
20
2020
SERVO_
RATE (*1)
21
2021
ACT_FAIL_
ACTION
22
2022
ACT_MAN_ID 0
23
2023
ACT_MODEL
_NUM
24
2024
ACT_SN
25
2025
VALVE_MAN
_ID
26
2026
VALVE_
MODEL
_NUM
27
2027
VALVE_SN
28
2028
VALVE_TYPE 1
29
2029
XD_CAL_
LOC
30
2030
XD_CAL_
DATE
31
2031
XD_CAL_
WHO
32
2032
ALARM_
SUM
Table 61 Transducer Block Parameters (Continued)
Default
Name
(factory
setting)
120
15 sec
0. 22 sec
1
Null
0
0
Null
0
Null
01/01/00
Null
FVP 110 Fieldbus Valve Positioner Manual
Write
O/S
Static control loop gain set by auto tuning [0.5
to 1300 ]
O/S
Integral time set by auto tuning.
O/S
Derivative time set by auto tuning.
O/S
Specifies the actuator action direction (in case
of losing of air supply pressure):
1 = Air to Open
2 = Air to Close
ID of actuator manufacturer
Model number of actuator
Serial number of actuator
ID of valve manufacturer
Model number of valve
Serial number of valve
O/S
Valve type:
1 = linear-motion valve
2 = rotary-motion valve
Shows and is used to record the location where
the positioner was calibrated.
Shows and is used to record the date when the
positioner was calibrated.
Shows and is used to record the person who
calibrated the positioner.
Shows the alarm summary (current alarm
statuses, acknowledged/unacknowledged
states, masking states) for the transducer
block.
190
Description