GE FVP110 Maintenance Manual page 202

Table of Contents

Advertisement

GE Energy
Relative
Index
Parameter
Index
23
1023
NV_CYCLE_
T
24
1024
FREE_
SPACE
25
1025
FREE_TIME
26
1026
SHED_RCAS
27
1027
SHED_ROUT 640000
28
1028
FAULT_
STATE
29
1029
SET_FSTATE 1
30
1030
CLR_FSTATE 1
31
1031
MAX_NOTIFY 3
32
1032
LIM_NOTIFY
33
1033
CONFIRM_
TIM
34
1034
WRITE_
LOCK
35
1035
UPDATE_
EVT
36
1036
BLOCK_ALM
Table 60 Resource Block Parameters (Continued)
Default
Name
(factory
setting)
0
0
0
640000
1
3
20000 (ms)
Unlocked
FVP 110 Fieldbus Valve Positioner Manual
Write
Cycle of saving the settings of non-volatile
attribute parameters to the EEPROM. 0 is set
with the FVP110, and saving is not cyclically
done.
Shows the free space memory for
configurations as a percent value. FVP110
shows zero which means the pre-configured
resource.
Shows the free time that can be used for
computations by resources but not supported
by the FVP110.
Communication time-out setting for
communications with the device from which the
remote cascade setpoint is sent.
Communication time-out setting for
communications with the device from which the
remote output setting is sent; not used in the
FVP110, however.
Indicates the fault-state.
Sets the fault-state.
Clears the fault-state.
Maximum number of alerts retained in the
device (FVP110).
Maximum number of alerts to be held by the
device (YVP110); used by the user to restrict
the number of alert notifications to the host to
prevent overflow of alert receptions in the host.
Defines the time to wait for confirmation for an
alert.
Prohibits write access from outside the device
to the settings.
Shows the contents of an update event upon
occurrence.
Shows the contents of an alarm event upon
occurrence.
186