11.1.2

Configuring with Profibus master

A connected PDP master can replace the existing node number with a new one. To
do this, no other slave can be connected to Profibus.
11.1.3

Starting the Profibus master

The left fieldbus activity indicator lights up one the Profibus master has activated
the SLK on the bus. The right fieldbus activity indicator flashes when commands are
being transmitted to the Profibus.
Fig. 34: The left fieldbus activity indicator lights up on the display

11.2 Starting up Interbus

The following steps are necessary to start up the ID 40 system on Interbus:
• Connect the SLK to Interbus, connect the 24 V supply voltage.
• Configure the outgoing remote bus signals depending on the position of the SLK on
Interbus, see Chapter 11.2.1 "Outgoing remote bus configuration".
Alternatively, the Interbus terminating bridge can be used as described in that
same chapter.
• Configure the desired maximum possible PDU size if the default value of 240 is not
desired.
• Start up the Interbus with the IBS CMD SWT G4 software by Phoenix Contact. See
Phoenix Contact for information on this program.
11.2.1

Outgoing remote bus configuration

If there are no other bus users on an ID 40/SLK-IBS, the outgoing remote us cannot
be routed. In common Interbus devices, this is detected at the output of the Interbus
bus connection using a jumper.
Since the ID 40/SLK uses a 5-pin M12 plug to save space, there is no pin available
for the standard RBST signal to turn off the outgoing remote bus. This is why the
outgoing remote bus is configured via the RS232 interface using the ID 40/KONF
program.
11.2.1.1 Outgoing remote bus configuration using browser
The ID 40/SLK homepage supports configuring the outgoing remote bus (see also
Chapter 10.5.6 "Fieldbus settings page").
1.
ibs.outgoing is preselected by choosing the selection box under Set.
2.
Enter the value 0 or 1 in the "Value" field.
Start-up and parameterization 153/176
3 842 530 344/2014-05, MIT: ID 40, Bosch Rexroth AG